Plan Review Notes
Plan Review Notes For Permit 08030053
Permit Number 08030053
Review Stop P
Sequence Number 2
Notes
Date Text
2008-04-11 14:54:52PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THERE ARE TWO DIFFERENT SIGNATURES ON THE ENGINEER
 SEAL ON DIFFERENT SHEETS. THE ENGINEER WHOSE NAME
 APPEARS ON THE TITLE BLOCK MUST SIGN, DATE AND SEAL THE
 DOCUMENTS. PER 61G15-230..2 FAC.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  