| 2008-04-15 12:15:18 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.PLEASE INCORPORATE POOL SAFETY REQUIREMENTS INTO |
| | THE PLAN, FBC R4101.17. |
| | |
| | THE ENGINEER SUBMITTED WHAT IS EFFECTIVELY AN AFFIDAVIT |
| | STATING THAT THE HOMEOWNER AGREES TO COMPLY WITH |
| | FBC4101.THE COMMENT REQUESTED THAT THE DESIGN |
| | CRITERIA BE INCORPORATED.CODE SECTIONS CANNOT BE |
| | CITED IN LIEU OF PROVIDING DESIGN CRITERIA; PLANS ONLY |
| | SAY "BARRIER" BUT BARRIER REQUIREMENTS ARE NOT STATED. |
| | PLEASE STATE DESIGN CRITERIA, EITHER AS OPTIONS OR |
| | SPECIFIC TO THIS JOB. |
| | |
| | NEW COMMENT: |
| | |
| | 2.SEE OTHER REVIEWERS' COMMENTS REGARDING THE |
| | SIGNATURES ON PLANS.PLEASE NOTE THAT, WHEN PLANS ARE |
| | SUBMITTED WITH SUCH OBVIOUSLY DIFFERENT SIGNATURES, WE |
| | ARE OBLIGATED TO CONFIRM THAT ALL PLANS WERE INDEED |
| | SIGNED AND SEALED BY THE ENGINEER FOR THE PROTECTION OF |
| | THE OWNER AND THE ENGINEER.IF THE ENGINEER MAKES A |
| | HABIT OF USING DIFFERENT SIGNATURES ROUTINELY, PERHAPS |
| | HE MIGHT CONSIDER INCLUDING A COVER LETTER ADDRESSING |
| | THIS ISSUE WITH EXAMPLES.ALTERNATIVELY, PLEASE |
| | PROVIDE SOME CONSISTENCY, ESPECIALLY WITHIN A PERMIT |
| | PACKAGE (ALL DOCUMENTS WITHIN ONE PERMIT APPLICATION |
| | SHOULD HAVE SIGNATURES WHICH ARE SIMILAR TO EACH |
| | OTHER). |