Plan Review Notes
Plan Review Notes For Permit 08030042
Permit Number 08030042
Review Stop B
Sequence Number 2
Notes
Date Text
2008-04-01 11:56:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3,
 PROVIDE CALCULATIONS.
  
 COMPLETE THE ATTACHED INSTALLATION SCHEDULE.IT WAS
 RETURNED BLANK.TWO COMPLETED SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 NEW COMMENT:
  
 THE FLOOR PLAN DESIGNATES SHUTTER TYPE BY COLOR.ALL
 PLANS MUST BE IN BLACK AND WHITE AS COLORS DO NOT
 APPEAR WHEN SCANNED FOR RECORD RETENTION.