Plan Review Notes
Plan Review Notes For Permit 08030038
Permit Number 08030038
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-05 17:56:161. THE ENTIRE FIRE SPRINKLER SYSTEM INSTALLATION TO
 COMPLY WITH NFPA 13.
  
 2. CAPS ARE TO BE PROVIDED ON THE FIRE DEPARTMENT
 CONNECTION (FDC).
  
 3. THE SWIVELS ON THE FIRE DEPARTMENT CONNECTION (FDC)
 ARE TO OPERATE CORRECTLY.
  
 4. ALL NEW FIRE SPRINKLER PIPING SHALL BE PRESSURE
 TESTED AT TWO HUNDRED PSIG.
  
 5. THE FIRE SPRINKLER SYSTEM INSTALLATION WHEN COMPLETE
 SHALL PROVIDE THE NECESSARY PROTECTION AS WAS
 INTENDED.
  
 6. THE ENTIRE SYSTEM IS TO BE INSPECTED, TESTED, AND
 APPROVED BY THE BUREAU OF FIRE PREVENTION
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX