| Plan Review Notes For Permit 08030038 |
| Permit Number |
08030038 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-05 17:56:16 | 1. THE ENTIRE FIRE SPRINKLER SYSTEM INSTALLATION TO | | | COMPLY WITH NFPA 13. | | | | | | 2. CAPS ARE TO BE PROVIDED ON THE FIRE DEPARTMENT | | | CONNECTION (FDC). | | | | | | 3. THE SWIVELS ON THE FIRE DEPARTMENT CONNECTION (FDC) | | | ARE TO OPERATE CORRECTLY. | | | | | | 4. ALL NEW FIRE SPRINKLER PIPING SHALL BE PRESSURE | | | TESTED AT TWO HUNDRED PSIG. | | | | | | 5. THE FIRE SPRINKLER SYSTEM INSTALLATION WHEN COMPLETE | | | SHALL PROVIDE THE NECESSARY PROTECTION AS WAS | | | INTENDED. | | | | | | 6. THE ENTIRE SYSTEM IS TO BE INSPECTED, TESTED, AND | | | APPROVED BY THE BUREAU OF FIRE PREVENTION | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|