| Notes |
| Date |
Text |
| 2008-03-05 11:42:50 | 2004 FBC W/2007 REVISIONS | | | ROOF OVER | | | | | | DENIED BY BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE LISTED IN THE PRODUCT | | | APPROVAL IS TOO LOW FOR THE CORNER AND PERIMETER AREAS. | | | SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING FROM | | | A FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED | | | ROOF CONSULTANT. SEE LIMITATION NUMBER 7 ON PAGE 30 OF | | | THE NOA. | | | | | | 2) THE ROOF WILL BE REQUIRED TO HAVE A PRE-INSPECTION | | | PERFORMED BY THE CITY BUILDING DEPARTMENT. | | | | | | 3) A RECORDED COPY OF THE NOC WILL BE REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|