| 2008-05-05 14:01:45 | ** DENIEDAUDIT ** |
| | |
| | 1) NOTE: PLEASE SEE THE NOTICE TO BUILDING OFFICIAL |
| | NEEDS TO COORDINATE WITH THE SIGNED AFFIDAVITS. PLEASE |
| | SEE THESE SHOW SEPARATE PRIVATE PROVIDERS AS THE |
| | RESPONSIBLE ENGINEERS. |
| | PLEASE SUBMIT. |
| | FS 553.791 |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS ARE STILL IN NEED OF MEETING FBC |
| | 13-415.2.ABC.1.1, .1.2, 13-415.2 |
| | PLEASE SEE FOR EXAMPLE: |
| | PLEASE SEE TRACK FIXTURE WHICH IS NOTED AS USING 40W |
| | FIXTURE. HOWEVER THE WATTAGE REQUIRED BY CODE IS BASE |
| | DON THE MAXIMUM FIXTURE VA NOT THE RATING OF THE BULB. |
| | AS THE FIXTURE LEGEND LIST MULTIPLE FIXTURES INCLUDING |
| | FIXTURES WHICH CONTAIN A HIGHER VA RATING, THEN THE |
| | HIGHER SHALL BE USED. |
| | PLEASE DELETE ALL OTHER FIXTURES OR FIGURE AT THE |
| | HIGHER VA. |
| | THE VA IS BASED ON THE LENGTH OF TRACK AT 30VA PER FT |
| | *OR* THE VA OF FIXTURE/TRANSFORMER WHICH EVER IS |
| | GREATER. |
| | PLEASE EXPLAIN WHY THE CALCULATIONS TABLE FOR LIGHTING |
| | NEXT TO FIXTURES TA AND T2 STATE * USE TRACK LENGTH* |
| | WHEN THE CALCULATIONS FOR THESE TWO FIXTURES SHOW USE |
| | OF THE FIXTURE VA? |
| | |
| | ** THIS ONE EXAMPLE ONLY. |
| | |
| | 3) NOTE: PLEASE SEE SECTIONS 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. PLEASE SEE THE OVER RIDE LOCATIONS ARE REQUIRED |
| | WHERE THE OCCUPANT ENTERS A SPACE/AREA. THE OCCUPANT IS |
| | REQUIRED TO CLEARLY SEE THE LIGHTING WHICH IS BEING |
| | CONTROLLED OR MEET THE EXCEPTIONS. |
| | RESPONSE MENTIONS THIS IS AN* ENCLOSED MALL* AND THERE |
| | IS NO OUTSIDE LIGHTING HOWEVER THIS IS NOT AN ENCLOSED |
| | MALL AND PLANS DO SHOW FIXTURES OUTSIDE FRONT DOORS. |
| | PLEASE VERIFY THE LOCATION OF THE SCOPE OF WORK. THIS |
| | AHJ DOES KNOW THE LOCATION OF THE PROPOSED SCOPE OF |
| | WORK.SEE COMMENTS BELOW AS INDOOR RATED FIXTURES |
| | SHALL NOT BE USED OUTSIDE. |
| | PLEASE SEE 13-415.1.ABC.1.4 AND ADJUST CONTROLS |
| | ACCORDINGLY. |
| | PLEASE SEE THE LIGHTING CONTROL INFORMATION PROVIDED IS |
| | NOT COMPLETE FOR REVIEW FOR CODE COMPLIANCE. |
| | THE EQUIPMENT APPEARS AS A LIGHTING PANEL BOARD HOWEVER |
| | NO INFORMATION/DETAILS WAS SHOWN TO SUPPORT OR |
| | DETERMINE MINIMUM CODE COMPLIANCE. |
| | INFORMATION ON RESPONSE LETTER CAN NOT DETERMINE CODE |
| | COMPLIANCE ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE SECTION NOTED ABOVE FOR EXTERIOR |
| | LIGHTS PER 13-415.1.ABC.1.4. |
| | PLEASE COMPLETE WITH ONE OF THE TWO MINIMUM REQUIRED BY |
| | CODE. |
| | |
| | 5) NOTE: PLEASE KNOW AS NOTED ABOVE IN NOTE #3 THE |
| | OUTSIDE LIGHT FIXTURES SHALL BE LISTED FOR LOCATION. |
| | THESE ARE OUTSIDE AND THE LOCATION IS NOT AN ENCLOSED |
| | MALL. |
| | PLEASE ADJUST LIGHT FIXTURE TYPES ACCORDINGLY. |
| | 110.3, 410.4A |
| | |
| | 6) NOTE: PLEASE SEE NOTICE WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE IS GIVEN AS PER FS |
| | 553.80(2)(B). |
| | THIS IS ONLY A NOTICE AT THIS TIME. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |