| 2008-03-04 11:55:25 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A00.0 RESTROOM REQUIREMENTS INDICATE UNISEX |
| | TOILET ROOM PERMITTED PER EXCEPTION 4 OF SECTION 403.2. |
| | THE EXCEPTION IS ONLY APPROVED IN MERCANTILE |
| | OCCUPANCIES WITH TOTAL FLOOR AREA OF 3000SF OR LESS. |
| | THE GROSS AREA INDICATED AS 3273 DOES NOT ALLOW FOR |
| | THIS EXCEPTION. TWO TOILET ROOMS ARE REQUIRED PER TABLE |
| | 403.1. (SECTION 302.1.1 INCIDENTIAL USE AREAS. AREAS |
| | THAT ARE INCIDENTAL TO THE MAIN OCCUPANCY SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH THE MAIN OCCUPANCY OF THE |
| | PORTION OF THE SPACE IN WHICH THE INCIDENTAL USE AREA |
| | IS LOCATED). |
| | |
| | 2. SHT A05.1 PER SECTION 1210.2 WALLS WITH IN 2 FEET OF |
| | A WATERCLOSET SHALL HAVE A "SMOOTH, HARD, SURFACE". NO |
| | WALL COVERING INDICATED BY THE WATER CLOSET. PLEASE |
| | SHOW COMPLIANCE. |
| | |
| | 3. DEMO SINK SHOWS COLD WATER SUPPLY BUT NO SANITARY |
| | DRAINAGE IN THE PLUMBING RESPONSIBILITY SCHEDULE. |
| | PLEASE CLARIFY. SECTION 301.3 |
| | |
| | 4. ALL E, M & P SHEETS REQUIRE THE ADDRESS OF THE |
| | ENGINEER. THE ADDRESS INDICATED IN THE TITLE BLOCK DOES |
| | NOT REFLECT THE ADDRESS OF RECORD INDICATED IN THE |
| | STATE OF FLORIDA DBPR WEBSITE. PRIOR TO RESUBMITTING, |
| | PLEASE UPDATE EITHER THE TITLE BLOCKS OR THE DBPR |
| | WEBSITE TO REFLECT THE CORRECT ADDRESS OF THE ENGINEER. |
| | FAC 61G1-16.004(1) & FS 481.2055. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |