Plan Review Notes
Plan Review Notes For Permit 08030020
Permit Number 08030020
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-20 13:48:53*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE SCOPE OF WORK SHALL NOT INTERFERE/HINDER ACCESS
 TO AND (OR) EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRELANES, ETC).
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, SHOW/DISPLAY THE SUITE NUMBER
 FOR THIS TENANT SPACE.AS PER WEST PALM BEACH CODE,
 SUITE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALL
 AND CEILINGS IN TERMS OF CLASS A OR CLASS B.
  
 6.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH
 SATIFY THE 75' TRAVEL DISTANCE. THE SYMBOL FOR THE FIRE
 EXTINGUISHER SHOWN ON SHEET F02.1 MAKES IT DIFFICULT TO
 DISTINGUISH FROM OTHER ITEMS ON THAT FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE APPROPIATE PLAN SHEET)
 EACH COMMENT WAS ADDRESSED
  
  