| 2008-03-10 18:37:08 | 2008-03-10 18:37:08 |
| | |
| | ** DENIED** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE FLA-COM ENERGY CALCULATIONS |
| | SUBMITTED WHICH ARE IN NEED OF COORDINATION WITH THE |
| | LIGHTING ON THE ELECTRICAL PLANS. |
| | PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH |
| | THE IDR WHEN RESUBMITTING. PLEASE BE SURE TO SEE |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. |
| | PLEASE SEE 13-415.2.ABC.1( TRACK LTS, AND OTHER |
| | SPECIALTY LIGHTING SYSTEMS) |
| | PLEASE SEE SECTION 13-415.2.ABC.1.2 AS THE WATTAGE |
| | WHICH IS REQUIRED SHALL BE BASED ON THE LABELED FIXTURE |
| | WATTAGE AND NOT THE BULB WATTAGE INSTALLED. |
| | PLEASE SEE THE TRACK LIGHTING IS REQUIRED TO BE FIGURED |
| | AT THE FIXTURE WATTAGE PER UNIT OR LENGTH OF TRACK, |
| | WHICH EVER IS GREATER. PLANS STATE TO USE THE LENGTH OF |
| | TRACK HOWEVER BASED ON THE LENGTHS SHOWN ON PLANS THE |
| | INPUT DATA REPORT DOES NOT CORRELATE. (FOR EXAMPLE: |
| | TRACK LENGTHS ARE GREATER THAN 208FT) |
| | PLEASE SEE THE LENGTHS ON PLANS AND ADJUST. |
| | PLEASE SEE THE TOTAL WATTAGE IN THE DESIGN AS STATED ON |
| | E03.1 IS NOT THE ACTUAL TOTAL DESIGN ON PLANS. PLEASE |
| | SEE THE TOTAL DESIGN WATTAGE SHOWN ON THE SUMMARY |
| | SHEETS OF THE ENERGY CALCULATIONS IS NOT THAT AS SHOWN |
| | ON PLANS. |
| | PLEASE SEE THE DESIGN WATTAGE ON SHEET 4 OF 6 NOTES |
| | 7622W AND YET THE ALLOWANCE IS LISTED AS 5301.9 AND THE |
| | CRITERION IS 1382. PLEASE EXPLAIN HOW THIS IS |
| | POSSIBLE. |
| | PLEASE ALSO SEE THE NON SALES AREA ON SHEET 4 OF 6 |
| | NOTES *FINE MATERIAL STORAGE*. PLEASE SEE STORAGE AREA |
| | DOES NOT MEET *FINE STORAGE* AS NOTED IN THE CODE. |
| | PLEASE ALSO COORDINATE WATTAGE USE ON ALL OTHERS PLEASE |
| | SEE THE IDR ON THE SUBMITTED CALCULATIONS WHICH SHOWS |
| | NO LIGHTING FIGURED INTO THE REPORT. HOW IS THIS |
| | POSSIBLE WHEN THE PLANS CLEARLY SHOW EXTERIOR |
| | LIGHTING? |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH |
| | RESPECT TO THE ENERGY CALCULATIONS SUBMITTED. |
| | ** PLEASE BE SURE THE DESIGNER OF RECORD SIGNS DATES |
| | AND SEALS THE CERTIFICATION SHEETS ALONG WITH THE |
| | SIGNATURE FROM THE OWNER AGENT. |
| | FS 471.025, FBC 13-103.1.1.1 |
| | |
| | 2) NOTE:PLEASE ADJUST THE COLOR CODING FOR 277/480V |
| | SYSTEMS TO BROWN, PURPLE AND YELLOW. |
| | PLANS SHOWS YELLOW, PURPLE, YELLOW. |
| | THE CITY OF WEST PALM BEACH AND ALL SURROUNDING |
| | JURISDICTIONS CONTAINED LOCAL AMENDMENTS FOR THE LAST |
| | 20PLUS YEARS WHICH HAD THE ABOVE COLORING CODING. EVEN |
| | AS THE TECHNICAL AMENDMENTS ARE NOT LONGER IN AFFECT |
| | KEEPING WITH ALL OTHER WIRING SYSTEMS ALREADY PRESENT |
| | IN THIS JURISDICTION AS WELL KEEPING WITH THE |
| | ELECTRICAL SYSTEMS ALREADY ON SITE THE ABOVE WILL BE |
| | REQUIRED.THE NEC ONLY PROVIDES ORANGE FOR A HIGH-LEG |
| | OPEN DELTA SYSTEMS, WHICH 277/480V IS NOT. AS THE NEC |
| | DOES NOT PROVIDE ANY COLOR CODING THIS IS PER AHJ AS A |
| | LIFE SAFETY, FIRE HAZARD, AND PROPERTY DAMAGE SAFETY |
| | MEASURE. |
| | 90.4. |
| | |
| | 3) NOTE: PLEASE VERIFY THE NOTE #3 IN SECTION 26 51 00 |
| | ON SHEET E01.1 WHICH STATES ** THE ENERGY POLICY ACT OF |
| | 1992*?? |
| | PLEASE KNOW THAT ANY ENERGY CODE COMPLIANCE MEASURES |
| | SHALL BE ACCORDANCE WITH THE FLORIDA ENERGY CODE |
| | CHAPTER 13. |
| | |
| | 4) NOTE: PLEASE SEE SECTION 26 27 28 FOR SWITCHING |
| | DEVICES DOES NOT APPLY. |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| | .1.4. |
| | PLEASE SEE THAT NOT ENOUGH INFORMATION WAS SUBMITTED |
| | FOR LIGHTING CONTROL SYSTEM. |
| | PLEASE SHOW ALL OVER RIDE DEVICE LOCATIONS AS REQUIRED. |
| | FOR EXAMPLE REAR ENTRANCE AND OTHER LOCATIONS. PLEASE |
| | SEE PLANS ARE SHOWING STANDARD WALL SP SWITCHES IN SOME |
| | LOCATIONS WHICH IS NOT POSSIBLE WHEN THE MINIMUM FOR |
| | CODE COMPLIANCE REQUIRES AUTOMATED CONTROLS AND OVER |
| | RIDES. (FOR EXAMPLE: |
| | PLEASE SEE MISSING EXTERIOR LIGHTING CONTROLS. |
| | AN OCCUPANT IS REQUIRED TO VISUALLY SEE THE LIGHTING |
| | BEING CONTROLLED OR MEETING THE EXCEPTION OF PILOT |
| | LIGHTS ETC. |
| | PLEASE PROVIDE TIMED SCHEDULING AND MAXIMUM OVER RIDE |
| | TIMES. |
| | PLEASE SHOW A LAYOUT OF ZONES REQUIRED. |
| | ** PLEASE KNOW AS NOTED ABOVE REVIEW FOR LIGHTING |
| | COMPLIANCE CAN NOT BE DONE AS THERE ARE MISSING ITEMS. |
| | |
| | 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED IN THE |
| | LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70 |
| | (NEC). |
| | PLEASE SEE SHOW WINDOWS ARE NOW IN 220.43. (PLANS |
| | REFLECT 220.12) |
| | |
| | 7) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO CONTAIN |
| | MINIMUM RATINGS FOR HORN AND STROBE DEVICES MEETING FBC |
| | AND CHAPTER ADA REQUIREMENTS HOWEVER PLEASE SEE THE FA |
| | SHEETS AS THE STROBE RATINGS ARE NOTED AS CD AND ALSO |
| | SHOW CD ON LEGEND. |
| | PLEASE SEE FBC 11-4.28.3(4) FOR MINIMUM 75CD REQUIRED |
| | FOR ADA COMPLIANCE. |
| | |
| | 8) NOTE: PLEASE PROVIDE A MORE CLEAR LOCATION OF THE |
| | SERVICE EQUIPMENT/PANEL LOCATIONS. |
| | 240.24, 408.17,AND 110.26. |
| | IT IS NOT ENTIRELY CLEAR ON ELECTRICAL PLANS WHERE THIS |
| | EQUIPMENT IS LOCATED. |
| | |
| | 9) NOTE: PLEASE KNOW ANY LOCK OFF DEVICES AS NOTED ON |
| | PANEL SCHEDULE WILL BE REQUIRED TO BE LISTED FOR |
| | PERMANENT INSTALLATIONS AND NOT THE *CLICK OR SNAP ON* |
| | TYPE. SHALL BE LISTED ACCORDINGLY WHERE REQUIRED. MANY |
| | OF THE DEVICES ON THE MARKET ARE LISTED FOR TEMPORARY |
| | USE AS/ LOCK OUT/TAG OUT. |
| | SHALL BE AN INTEGRAL PART OF BREAKER OR LISTED AS |
| | SUCH. |
| | 110.3 |
| | |
| | 10) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS |
| | DOWN THE LEFT HAND SIDE OF PLANS. THESE HAVE BEEN |
| | REMOVED FROM THE REVIEWED SET. PLEASE PLACE DOCUMENTS |
| | IN SOME SORT OF FOLDER WITH LABELING OF TABS ETC. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |