Plan Review Notes
Plan Review Notes For Permit 08030020
Permit Number 08030020
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-10 18:37:082008-03-10 18:37:08
  
 ** DENIED**
  
  
  
 1) NOTE:PLEASE SEE THE FLA-COM ENERGY CALCULATIONS
 SUBMITTED WHICH ARE IN NEED OF COORDINATION WITH THE
 LIGHTING ON THE ELECTRICAL PLANS.
 PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH
 THE IDR WHEN RESUBMITTING. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3.
 PLEASE SEE 13-415.2.ABC.1( TRACK LTS, AND OTHER
 SPECIALTY LIGHTING SYSTEMS)
 PLEASE SEE SECTION 13-415.2.ABC.1.2 AS THE WATTAGE
 WHICH IS REQUIRED SHALL BE BASED ON THE LABELED FIXTURE
 WATTAGE AND NOT THE BULB WATTAGE INSTALLED.
 PLEASE SEE THE TRACK LIGHTING IS REQUIRED TO BE FIGURED
 AT THE FIXTURE WATTAGE PER UNIT OR LENGTH OF TRACK,
 WHICH EVER IS GREATER. PLANS STATE TO USE THE LENGTH OF
 TRACK HOWEVER BASED ON THE LENGTHS SHOWN ON PLANS THE
 INPUT DATA REPORT DOES NOT CORRELATE. (FOR EXAMPLE:
 TRACK LENGTHS ARE GREATER THAN 208FT)
 PLEASE SEE THE LENGTHS ON PLANS AND ADJUST.
 PLEASE SEE THE TOTAL WATTAGE IN THE DESIGN AS STATED ON
 E03.1 IS NOT THE ACTUAL TOTAL DESIGN ON PLANS. PLEASE
 SEE THE TOTAL DESIGN WATTAGE SHOWN ON THE SUMMARY
 SHEETS OF THE ENERGY CALCULATIONS IS NOT THAT AS SHOWN
 ON PLANS.
 PLEASE SEE THE DESIGN WATTAGE ON SHEET 4 OF 6 NOTES
 7622W AND YET THE ALLOWANCE IS LISTED AS 5301.9 AND THE
 CRITERION IS 1382. PLEASE EXPLAIN HOW THIS IS
 POSSIBLE.
 PLEASE ALSO SEE THE NON SALES AREA ON SHEET 4 OF 6
 NOTES *FINE MATERIAL STORAGE*. PLEASE SEE STORAGE AREA
 DOES NOT MEET *FINE STORAGE* AS NOTED IN THE CODE.
 PLEASE ALSO COORDINATE WATTAGE USE ON ALL OTHERS PLEASE
 SEE THE IDR ON THE SUBMITTED CALCULATIONS WHICH SHOWS
 NO LIGHTING FIGURED INTO THE REPORT. HOW IS THIS
 POSSIBLE WHEN THE PLANS CLEARLY SHOW EXTERIOR
 LIGHTING?
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH
 RESPECT TO THE ENERGY CALCULATIONS SUBMITTED.
 ** PLEASE BE SURE THE DESIGNER OF RECORD SIGNS DATES
 AND SEALS THE CERTIFICATION SHEETS ALONG WITH THE
 SIGNATURE FROM THE OWNER AGENT.
 FS 471.025, FBC 13-103.1.1.1
  
 2) NOTE:PLEASE ADJUST THE COLOR CODING FOR 277/480V
 SYSTEMS TO BROWN, PURPLE AND YELLOW.
 PLANS SHOWS YELLOW, PURPLE, YELLOW.
 THE CITY OF WEST PALM BEACH AND ALL SURROUNDING
 JURISDICTIONS CONTAINED LOCAL AMENDMENTS FOR THE LAST
 20PLUS YEARS WHICH HAD THE ABOVE COLORING CODING. EVEN
 AS THE TECHNICAL AMENDMENTS ARE NOT LONGER IN AFFECT
 KEEPING WITH ALL OTHER WIRING SYSTEMS ALREADY PRESENT
 IN THIS JURISDICTION AS WELL KEEPING WITH THE
 ELECTRICAL SYSTEMS ALREADY ON SITE THE ABOVE WILL BE
 REQUIRED.THE NEC ONLY PROVIDES ORANGE FOR A HIGH-LEG
 OPEN DELTA SYSTEMS, WHICH 277/480V IS NOT. AS THE NEC
 DOES NOT PROVIDE ANY COLOR CODING THIS IS PER AHJ AS A
 LIFE SAFETY, FIRE HAZARD, AND PROPERTY DAMAGE SAFETY
 MEASURE.
 90.4.
  
 3) NOTE: PLEASE VERIFY THE NOTE #3 IN SECTION 26 51 00
 ON SHEET E01.1 WHICH STATES ** THE ENERGY POLICY ACT OF
 1992*??
 PLEASE KNOW THAT ANY ENERGY CODE COMPLIANCE MEASURES
 SHALL BE ACCORDANCE WITH THE FLORIDA ENERGY CODE
 CHAPTER 13.
  
 4) NOTE: PLEASE SEE SECTION 26 27 28 FOR SWITCHING
 DEVICES DOES NOT APPLY.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
 PLEASE SEE THAT NOT ENOUGH INFORMATION WAS SUBMITTED
 FOR LIGHTING CONTROL SYSTEM.
 PLEASE SHOW ALL OVER RIDE DEVICE LOCATIONS AS REQUIRED.
 FOR EXAMPLE REAR ENTRANCE AND OTHER LOCATIONS. PLEASE
 SEE PLANS ARE SHOWING STANDARD WALL SP SWITCHES IN SOME
 LOCATIONS WHICH IS NOT POSSIBLE WHEN THE MINIMUM FOR
 CODE COMPLIANCE REQUIRES AUTOMATED CONTROLS AND OVER
 RIDES. (FOR EXAMPLE:
 PLEASE SEE MISSING EXTERIOR LIGHTING CONTROLS.
 AN OCCUPANT IS REQUIRED TO VISUALLY SEE THE LIGHTING
 BEING CONTROLLED OR MEETING THE EXCEPTION OF PILOT
 LIGHTS ETC.
 PLEASE PROVIDE TIMED SCHEDULING AND MAXIMUM OVER RIDE
 TIMES.
 PLEASE SHOW A LAYOUT OF ZONES REQUIRED.
 ** PLEASE KNOW AS NOTED ABOVE REVIEW FOR LIGHTING
 COMPLIANCE CAN NOT BE DONE AS THERE ARE MISSING ITEMS.
  
 6) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED IN THE
 LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70
 (NEC).
 PLEASE SEE SHOW WINDOWS ARE NOW IN 220.43. (PLANS
 REFLECT 220.12)
  
 7) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO CONTAIN
 MINIMUM RATINGS FOR HORN AND STROBE DEVICES MEETING FBC
 AND CHAPTER ADA REQUIREMENTS HOWEVER PLEASE SEE THE FA
 SHEETS AS THE STROBE RATINGS ARE NOTED AS CD AND ALSO
 SHOW CD ON LEGEND.
 PLEASE SEE FBC 11-4.28.3(4) FOR MINIMUM 75CD REQUIRED
 FOR ADA COMPLIANCE.
  
 8) NOTE: PLEASE PROVIDE A MORE CLEAR LOCATION OF THE
 SERVICE EQUIPMENT/PANEL LOCATIONS.
 240.24, 408.17,AND 110.26.
 IT IS NOT ENTIRELY CLEAR ON ELECTRICAL PLANS WHERE THIS
 EQUIPMENT IS LOCATED.
  
 9) NOTE: PLEASE KNOW ANY LOCK OFF DEVICES AS NOTED ON
 PANEL SCHEDULE WILL BE REQUIRED TO BE LISTED FOR
 PERMANENT INSTALLATIONS AND NOT THE *CLICK OR SNAP ON*
 TYPE. SHALL BE LISTED ACCORDINGLY WHERE REQUIRED. MANY
 OF THE DEVICES ON THE MARKET ARE LISTED FOR TEMPORARY
 USE AS/ LOCK OUT/TAG OUT.
 SHALL BE AN INTEGRAL PART OF BREAKER OR LISTED AS
 SUCH.
 110.3
  
 10) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS
 DOWN THE LEFT HAND SIDE OF PLANS. THESE HAVE BEEN
 REMOVED FROM THE REVIEWED SET. PLEASE PLACE DOCUMENTS
 IN SOME SORT OF FOLDER WITH LABELING OF TABS ETC.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-08 23:48:072008-03-08 23:48:07
  
 IN ELECTRIC FOR REVIEW