2008-03-12 16:56:59BUILDING PLAN REVIEW
 PERMIT: 08030020
 ADD: 700 S ROSEMARY AVE #110
 CONT: RUSSCO INC. GENERAL CONTRACTORS
 TEL: (508)989-3077/ NEYITA 856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. BATH & BODYWORKS
 NEW STOREFRONT CALCULATIONS INDICATE DESIGNED TO 2006
 FBC SUPPLEMENTS, PLEASE CORRECT.
  
 1F) SHEET S01.1 PLANSDO NOT REFER ONLY TO THE 2004
 FBC NOT THE 2007 SUPPLEMENTS.
  
 1G) SHEET S01.1 NOR THE STOREFRONT CALCULATIONS
 INDICATE THE PARAMETERS OF THE WIND DESIGN. 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 1H) SHEET S01.1UNDER THE HEADING SPECIAL INSPECTION
 REFERENCES THE IBC 1701, PLEASE CORRECT THE REFERENCE
 TO THE FBC. NOTE THE BUILDING OFFICIAL HAS DETERMINED
 THAT ?NO?
 THRESHOLD PLAN WILL BE NECESSARY FOR THE REPLACEMENT OF
 STOREFRONT SYSTEMS.
  
 2)THE BUILDING OFFICIAL HAS DETERMINED THAT THE CBC
 RUSSCO INC. GENERAL CONTRACTORS ARE WORKING OUT OF THE
 SCOPE OF THEIR LICENSE. FL S S 489.105 (B)
 BUILDING CONTRACTOR" MEANS A CONTRACTOR WHOSE
 SERVICES ARE LIMITED TO CONSTRUCTION OF COMMERCIAL
 BUILDINGS AND SINGLE-DWELLING OR MULTIPLE-DWELLING
 RESIDENTIAL BUILDINGS, WHICH COMMERCIAL OR RESIDENTIAL
 BUILDINGS DO NOT EXCEED THREE STORIES IN HEIGHT, AND
 ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING,
 REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE
 SERVICES DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING. SHEET S01.1 & S02.1 BOTH INDICATE STRUCTURAL
 MEMBERS THAT WILL AFFECT THE STOREFRONT SYSTEM AND THUS
 THE BUILDING ENVELOPE ITSELF.
  
 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
 ARCH ALUMINUM IMPACT WALL L-3000,REQUIRES FLORIDA
 COVERSHEET
 KAWNEER350-MS, REQUIRES FLORIDA COVERSHEET
  
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5)DOOR # 3 THAT LEADS INTO THE STORAGE ROOM HAS
 ISSUES WITH CLEAR FLOOR SPACE WITH THE LOCATION OF THE
 FIRE EXTINGUISHER AT THIS LOCATION, SEE 11-4.13.5 &
 11-4.4.1.
  
 6) CALCULATIONS WERE SUBMITTED FOR THE STOREFRONT BUT
 NO CALCULATIONS WERE SUBMITTED FOR THE FLOOR LOADING
 OVER THE RESTROOM. 110.4.2 ALL SUCH CALCULATIONS SHALL
 BE ACCOMPANIED BY AN AFFIDAVIT FROM THE ARCHITECT OR
 ENGINEER STATING THE SAFE ALLOWABLE FLOOR LOAD ON EACH
 FLOOR IN POUNDS PER SQ FOOT UNIFORMLY DISTRIBUTED. THE
 COMPUTATIONS AND AFFIDAVIT SHALL BE FILED AS A
 PERMANENT RECORD OF THE BUILDING DIVISION.
  
 7) SHEET A-801 INDICATESA DETAIL C/ A-803, THERE IS
 NO SECTION, PLANS ARE NOT CLEAR AS TO WHAT THE EXTERIOR
 WALLS ON EITHER SIDE OF THE FRONT ENTRY ARE MADE OF?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.