Plan Review Notes
Plan Review Notes For Permit 08020735
Permit Number 08020735
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-03 15:51:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE ADD AN A/C EQUIPMENT SCHEDULE WITH MAKE,
 MODEL NUMBERS, ETC, TO MECHANICAL PLAN, PER 2004 WPB
 AMEND. 106.3.5.4 (10).
  
 2) SEE YELLOW HIGH LIGHT ON MECH. PLAN SHOWING SUPPLY
 AIR DUCTS (FLEX) THAT NEED TO SIZED, PLEASE CORRECT PER
 2004 WPB AMEND. 106.3.5.4 (10).
  
 3) SEE YELLOW HIGH LIGHT ON MECH. PLAN SHOWING SUPPLY
 AIR GRILL WITH NO DUCK (FLEX), PLEASE CORRECT PER 2004
 WPB AMEND. 106.3.5.4 (10).
  
 4) SEE YELLOW HIGH LIGHT AT RETURN AIR GRILL NEAR AIR
 HANDLER NEEDS THE COMPLETE SIZE, IT IS ONLY SHOWING 24
 X __, PLEASE CORRECT.
  
 5) PLEASE SHOW THE LOCATION OF THE TWO GAS TANKLESS
 WATER HEATERS ON THE MECHANICAL PLAN, SEE 2004 FBC/FG
 304.1 AND 304.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]