| Plan Review Notes For Permit 08020735 |
| Permit Number |
08020735 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-03 15:51:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE ADD AN A/C EQUIPMENT SCHEDULE WITH MAKE, | | | MODEL NUMBERS, ETC, TO MECHANICAL PLAN, PER 2004 WPB | | | AMEND. 106.3.5.4 (10). | | | | | | 2) SEE YELLOW HIGH LIGHT ON MECH. PLAN SHOWING SUPPLY | | | AIR DUCTS (FLEX) THAT NEED TO SIZED, PLEASE CORRECT PER | | | 2004 WPB AMEND. 106.3.5.4 (10). | | | | | | 3) SEE YELLOW HIGH LIGHT ON MECH. PLAN SHOWING SUPPLY | | | AIR GRILL WITH NO DUCK (FLEX), PLEASE CORRECT PER 2004 | | | WPB AMEND. 106.3.5.4 (10). | | | | | | 4) SEE YELLOW HIGH LIGHT AT RETURN AIR GRILL NEAR AIR | | | HANDLER NEEDS THE COMPLETE SIZE, IT IS ONLY SHOWING 24 | | | X __, PLEASE CORRECT. | | | | | | 5) PLEASE SHOW THE LOCATION OF THE TWO GAS TANKLESS | | | WATER HEATERS ON THE MECHANICAL PLAN, SEE 2004 FBC/FG | | | 304.1 AND 304.5.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|