| Plan Review Notes For Permit 08020693 |
| Permit Number |
08020693 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-12-05 09:05:16 | ** PROVISO** | | | | | | | | | | | | 1) NOTE: WATER HEATER LOAD IN AMPERAGE NOT SHOWN | | | CORRECTLY. LOAD IS ALSO A CONTINUOUS LOAD UNDER 2005 | | | NEC 422.13. | | | | | | REVISE CALCULATIONS AND LOADS ALONG ON WATER HEATER. | | | THIS WILL BE NEEDED ALONG WITH ANY OTHER REVISIONS MADE | | | TO PLANS. | | | | | | IF THERE ARE QUESTIONS, PLEASE CALL. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|