| 2008-10-30 16:55:32 | |
| | |
| | ** DENIED REVIEW** |
| | |
| | ** A CALL WAS PLACED TO THE ENGINEER OF RECORD AT THE |
| | TIME OF THIS REVIEW HOWEVER WAS NOT IN THE OFFICE. A |
| | MESSAGE WAS LEFT SO THESE ITEMS BELOW COULD BE GONE |
| | OVER. PLANS ARE COMING BACK WITH COMMENTS FROM OTHER |
| | TRADES |
| | |
| | 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS CAN NOT BE |
| | STAMPED OR SIGNED OFF BY ELECTRICAL AS THERE ARE ERRORS |
| | WITH OTHER COMPONENTS TO THE BUILDING WHICH DO NOT |
| | COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES. |
| | (BUILDING) |
| | EXAMPLE WOULD BE THE FLOORS WHICH ARE USING CARPET AND |
| | RUBBER PADDING WHERE THE FINISH SCHEDULE ON THE C SHEET |
| | INDICATE CONCRETE, TILE, ETC |
| | THE IDR NEEDS TO INDICATE THE WATER HEATER SIZE WHICH |
| | COORDINATES WITH PLANS. SEE NEXT COMMENT FOR LOADS. |
| | FBC 13-400.3A |
| | |
| | 2) NOTE: PLEASE SEE THE LOADS WHICH ARE SHOWN ON THE |
| | PANEL SCHEDULES ARE IN QUESTION. THE PANEL INDICATES |
| | LOADS BY *AMPS* FOR EACH PHASE HOWEVER PLEASE SEE SMALL |
| | APPLIANCE(S), MICROWAVE AND OTHER SIMILAR ITEMS WHICH |
| | ARE SHOWN AS 1.5AMPS, 1.2 AMPS ETC. IS THIS NOT KVA? |
| | PLEASE SEE PANEL *A* FOR EXAMPLE: |
| | PLEASE SEE THE LOAD FOR THE WATER HEATER WHICH STATES |
| | 20.0AMPS PER PHASE. WHAT SIZE OF WATER HEATER IS THIS? |
| | PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH HAS BEEN |
| | REVISED TO CONSIDER STORAGE TYPE WATER HEATERS AS |
| | CONTINUOUS LOADS. THIS WOULD REQUIRE LOAD CALCULATIONS |
| | TO SHOW 125% FOR THIS UNIT. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |