| Plan Review Notes For Permit 08020693 |
| Permit Number |
08020693 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-31 15:10:16 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS, | | | FIRE LANES) | | | | | | 3. ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS | | | EAST TAMARIND AVENUE, DISPLAY THE NUMERICAL ADDRESS OF | | | THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESS | | | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS | | | THAN 1" IN WIDTH. | | | | | | 4. PROVIDE THE FOLLOWING INFORMATION: * WILL THE | | | BUILDING BE OCCUPIED BY A SINGLE TENANT OR MULTIPLE | | | TENANTS, * OCCUPANCY TYPE FOR EACH TENANT SPACE, * | | | OCCUPANT LOAD FOR EACH TENANT SPACE, * IS THE BUILDING | | | FIRE SPRINKLERED OR NOT? | | | | | | 5. IT IS NOTED ON SHEET C1 OF "FIRE ALARM PERMIT BY | | | OTHERS". DOES THE BUILDING HAVE A FIRE ALARM SYSTEM? IF | | | SO, PROVIDE A LAYOUT OF THE SYSTEM. | | | | | | 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL | | | DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|