| 2008-03-11 12:59:34 | ** DENIED** |
| | |
| | FIRST REVIEW UNDER NEW PERMIT APPLICATION FOR THIS |
| | ADDRESS. |
| | PREVIOUS REVIEW WAS DONE UNDER APPLIED # 07030453 WHICH |
| | HAS NOW EXPIRED. |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE FOLLOWING CODES SHALL BE |
| | STATED ON PLANS. NEEDS TO BE ON ELECTRICAL PLANS AS |
| | WELL AS COVER SHEET. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (PLANS SHOW 2004) |
| | |
| | 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUESTED |
| | ON PREVIOUS REVIEW. AS THESE WERE NOT SUBMITTED NO |
| | REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME. |
| | PLEASE SEE 13-101.1.2, 13-400.3.B, 13-400.3.C, |
| | 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 AND .1.4 FOR |
| | MISSING LIGHTING CONTROLS. |
| | PLEASE BE SURE TO SEE AUTOMATED CONTROLS REQUIRED IN |
| | .1.2 FOR INTERIOR LOCATIONS AS NOTED IN THE CODE. |
| | PLEASE BE SURE TO PROVIDE THE INFORMATION FOR EXTERIOR |
| | CONTROLS AS REQUIRED IN .1.4 AS NOTED ABOVE. |
| | |
| | 4) NOTE: PLEASE SEE E-2 AS THIS WAS PRINTED AND MUCH OF |
| | THE INFORMATION ON PANEL SCHEDULE FOR LOADS, CIRCUITING |
| | ETC IS BLURRY AND NOT EASILY READ. |
| | PLEASE REPRINT WITH MORE CLARITY. |
| | FBC 106.1 |
| | |
| | 5) NOTE: PLEASE SEE SERVICE RISER ONLY SHOWS ONE RISER |
| | AND ONLY ONE SET OF CONDUCTORS. THERE IS PART OF THE |
| | CONDUCTORS WHICH NOTES *EACH* HOWEVER NO INFORMATION ON |
| | IF THERE ARE PARALLEL RISERS. |
| | PLEASE SHOW FOR PARALLEL CONDITIONS AS REQUIRED. |
| | 240.4, 310.16 |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE IS NOTED TO |
| | STRUCTURAL STEEL HOWEVER IS ALSO REQUIRED TO FOOTER |
| | STEEL PER 250.50 |
| | |
| | 7) NOTE: PLEASE SEE RISER IS MISSING ANY METERING |
| | DEVICE? METER CAN, CT ETC. |
| | PLEASE CONTACT FPL FOR SERVICE REQUIREMENTS AND SEE FPL |
| | MINIMUM SERVICE SPECIFICATIONS. THIS INFORMATION CAN BE |
| | FOUND AT FPL WEBSITE. |
| | HTTP://WWW.FPL.COM/DOINGBUSINESS/BUILDER/B1_INDEX.SHTML |
| | |
| | |
| | 8) NOTE: PLEASE PROVIDE THE ACTUAL AIC RATING OF THE |
| | EQUIPMENT. THE PLANS INDICATE THE AVAILABLE FAULT |
| | CURRENT AT SERVICE ETC HOWEVER DOES NOT PROVIDE RATINGS |
| | ON EQUIPMENT. |
| | 110.9, 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE PLACE THE REQUIRED DISCONNECTS FOR ANY |
| | ROOF-TOP A/C EQUIPMENT ON ELECTRICAL PLANS. |
| | 440.11 |
| | |
| | 10) NOTE: PLEASE SEE 210.63 AND 210.8B FOR GFI REQUIRED |
| | FOR ANY ROOF-TOP AC EQUIPMENT. |
| | |
| | 11) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL |
| | FIXTURES ON PLANS. |
| | PLEASE BE SURE TO SEE NOTE #2 FOR COORDINATION WITH THE |
| | ENERGY CALCULATIONS TO BE SUBMITTED. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 12) NOTE: PLEASE SEE SEVERAL NOTES ON E-3 STATES THERE |
| | MAY BE SOME SORT OF FIRE ALARM SYSTEM HOWEVER NO SYSTEM |
| | COULD BE LOCATED ON PLANS. |
| | THERE ARE ALSO NOTES WHICH STATES THE HORN AND STROBE |
| | LEVELS SHALL MEET NFPA-72, HOWEVER PLEASE SEE FBC |
| | 11?4.28.1, .2 AND .3(4) FOR MINIMUM LOCATIONS AND |
| | LEVELS FOR FBC ADA. |
| | |
| | 13) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET |
| | NEC 220. |
| | PLEASE SEE PANEL *A* FOR EXAMPLE*: HOW ARE THE |
| | APPLIANCE LOADS BEING FIGURED? |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC. |
| | CONTINUOUSLOADS WERE SHOWN AT 125%. |
| | |
| | 14) NOTE: PLEASE SEE THE PLANS NEED TO IDENTIFY THE |
| | LOCATION OF PANEL *A* AS AN ELECTRICAL ROOM. THIS MAY |
| | NOT BE A CLOSET. |
| | SIGNAGE WILL ALSO BE REQUIRED. |
| | 110.26, 240.24, 408.17 ETC |
| | FBC 106.1.2 |
| | |
| | *** AS NOTED, AS THERE SOME ITEMS NOT YET SUBMITTED A |
| | FULL AND COMPLETE REVIEW CAN NOT BE DONE.PLEASE KNOW |
| | THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |