Plan Review Notes
Plan Review Notes For Permit 08020683
Permit Number 08020683
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-08 19:33:51** DENIED **
  
 ** 400 S. AUSTRALIAN AVE.
 PERMIT #08020683
  
 1) NOTE: PERMIT APPLICATION SUBMITTED IS TO INSTALL NEW
 GENERATOR HOWEVER NO PLANS WERE SUBMITTED WITH THE
 SEPARATE PERMIT APPLICATION PACKAGE.
 SUBMIT COMPLETE PLANS, RISER, ETC
 PLEASE SEE NFPA-70 2005, NFPA-110 2002, NFPA-30,
 NFPA-101 ETC.
  
 2) NOTE: PLEASE KNOW THEVALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF
 ANY OF THESE ARE OWNER SUPPLIED. THIS INCLUDES THE
 GENERATOR, ATS ETC.
  
 ** AS PERMIT APPLICATION WAS SUBMITTED WITH OTHER
 PERMIT APPLICATIONS FORTHIS SAME LOCATION, PLEASE SEE
 ANY NOTES UNDER OTHER PERMITS WHICH WILL AFFECT OTHER
 REVIEWS.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]