| 2008-03-08 19:33:51 | ** DENIED ** |
| | |
| | ** 400 S. AUSTRALIAN AVE. |
| | PERMIT #08020683 |
| | |
| | 1) NOTE: PERMIT APPLICATION SUBMITTED IS TO INSTALL NEW |
| | GENERATOR HOWEVER NO PLANS WERE SUBMITTED WITH THE |
| | SEPARATE PERMIT APPLICATION PACKAGE. |
| | SUBMIT COMPLETE PLANS, RISER, ETC |
| | PLEASE SEE NFPA-70 2005, NFPA-110 2002, NFPA-30, |
| | NFPA-101 ETC. |
| | |
| | 2) NOTE: PLEASE KNOW THEVALUE SHALL INCLUDE ALL |
| | LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF |
| | ANY OF THESE ARE OWNER SUPPLIED. THIS INCLUDES THE |
| | GENERATOR, ATS ETC. |
| | |
| | ** AS PERMIT APPLICATION WAS SUBMITTED WITH OTHER |
| | PERMIT APPLICATIONS FORTHIS SAME LOCATION, PLEASE SEE |
| | ANY NOTES UNDER OTHER PERMITS WHICH WILL AFFECT OTHER |
| | REVIEWS. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | |