| Date |
Text |
| 2008-03-24 09:53:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.THE SITE PLAN SHOWS THIS AS TWO LOTS, OUR RECORDS |
| | SHOW ONE LOT.SEE ZONING COMMENTS REGARDING THE NEW |
| | PLAT. |
| | |
| | 2.SEVERAL PLANS WERE SUBMITTED FOR THIS ADDRESS, AND |
| | THERE WERE SOME REFERENCES TO BRADLEY PLACE AND |
| | SEMINOLE.PLEASE VERIFY ALL EASEMENT AND ADDRESS |
| | REFERENCES AND REVISE AS NECESSARY. |
| | |
| | 3.SEPARATE PERMITS REQUIRED (INFORMATIONAL ONLY). |
| | |
| | 4.DECLARE GOVERNING CODE, INCLUDING 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 5.DECLARE WIND DESIGN CRITERIA FBC1603.1.4. |
| | |
| | 6.PROVIDE ANCHORING INFORMATION TO COMPLY WITH |
| | FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS, |
| | AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE |
| | SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING, |
| | UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS |
| | FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF |
| | THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD |
| | LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| | DURING A DESIGN WIND EVENT SHALL BE USED. |
| | |
| | 7.ONE SHEET STATES THIS IS A KOHLER, ANOTHER STATES |
| | CATEPILLAR.ONE SHEET STATES THIS IS NON LIFE SAFETY |
| | GENERATOR, THE OTHER STATES THIS IS A LIFE SAFETY |
| | GENERATOR.PLEASE PROVIDE CONSISTENT INFORMATION ON |
| | THE PLANS. |
| | |
| | 8.PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL |
| | DIMENSIONS AND STRUCTURAL INFORMATION. |
| | |
| | |
| | |
| | |