| Plan Review Notes For Permit 08020680 |
| Permit Number |
08020680 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-29 07:11:14 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | INDICATE COMPLIANCE WITH THE FOLLOWING: | | | | | | 1} 225.31 DISCONNECTING MEANS | | | MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL | | | UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE | | | BUILDING OR STRUCTURE. | | | 225.32 LOCATION | | | THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER | | | INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED | | | OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR | | | STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A | | | READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | | ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS | | | SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|