2008-02-29 07:11:14 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 INDICATE COMPLIANCE WITH THE FOLLOWING:
  
 1} 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE
 BUILDING OR STRUCTURE.
 225.32 LOCATION
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS
 SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  