2008-03-06 14:34:02RESIDENTIAL GARAGE ADDITION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE DONE AT A LATER TIME AT TIME OF
 PERMIT PICK TO AVOID EXPIRATION OF DOCUMENT.
  
 2-OWES $146.78.PERMIT VALUATION WAS UPDATEDTO
 $13,505AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO
 FBC 2004.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SWING DOOR AS SHOWN ON PLANS.
 ***NOTE: MAKE SURE PRODUCT APPROVAL HAS DOOR THAT
 RESISTSTHE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER.
  
 B) GARAGE DOOR:
 * NEED PRODUCT APPROVAL FOR GARAGE DOORTHAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER. PRODUCT
 APPROVAL SUBMITTED DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 ** FLORIDA PRODUCT APPROVALFL 4913 AND NOA 03-0507.08
 DON'T CORRESPOND TO EACH OTHER.PROVIDE COMPLETE
 PRODUCT APPROVAL EITHER FROM THE FLORIDA WEBSITE OR
 COMPLETE NOA THAT MEETS THE CALCULATED DESIGN
 PRESSURES.
  
 C) SINGLE HUNG WINDOWS. NOA02-0507.06 EXPIRED ON
 11/14/2007. NEED TO PROVIDECURRENT NOA.
  
 NOTE: FL239-R10 AND NOA 02-0507.06 DON'T CORRESPOND TO
 EACH OTHER. PROVIDECOMPLETE INFORMATION FOR EITHER
 ONE.
  
 D) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS AND
 DETAILS.
 NOTE: PROVIDE ONLY THE COVER PAGE AND PAGE WHERE
 CONNECTOR IS SHOWN.
  
 E) STORM SHUTTERS (SINCE SINGLE HUNG WINDOW HAS NOT
 IMPACT GLASS).
 NOTE:CLEARLY MARK ON PRODUCT APPROVAL SPECIFIC
 MOUNTING CONDITIONS (EG: WALL MOUNTED) AND CONNECTOR
 TYPE AND SPACING TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, PANEL SPAN AND STRUCTURE TO
 BE ATTACHED TO (CONCRETE BLOCK). SEE INSTALLATION
 SCHEDULES ON INSIDE OF STORM SHUTTERS DRAWINGS AND MARK
 CORRESPONDING INFORMATION.
  
 4- SHEET A1:
 A) WIND PRESSURES ZONESROOF DIAGRAM DOESN'T
 CORRESPOND THE TYPE OF ROOF SHOWN. REVISE AS REQUIRED.
 SEE SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE AND
 REVISE AS REQUIRED.
 ALSO, REVISE REFERENCED SECTION OF CODE. SEE 2004
 FLORIDA RESIDENTIAL CODE FOR CORRECT SECTIONS TO BE
 CITED.
  
 B) SPECIFY ROOF SHEATHING NAILING AS REQUIRED BY
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 NOTE: MAKE SURE ALL ROOF NAILING ZONES ARE IDENTIFIED
 WITH RESPECTIVE NAILING SIZE, TYPE AND SPACING.
  
 C) WHERE IS FASTENER SCHEDULE INFORMATION TAKEN
 FROM.SEE CURRENT SIMPSON CATALOG AND REVISE AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCEWITH SEC. R301.
  
 ALSO, CLARIFY WHYTHE LATERAL LOADS ARE NEG'L AND WHAT
 IT STANDS FOR?. SEC. 106.1.2 CITY AMENDMENT STO FBC
 2004 TO VERIFY COMPLIANCE WITH DESIGN LOADS OF SEC.
 R301.
  
 D) BUILDING INFORMATION AT BOTTOM OF PAGE:
 * BULDING WIDTH IS INCORRECT.
 ** BUILDING LENGTH IS INCORRECT.
 *** ROOF SLOPE IS INCORRECT.
 **** DESIGN PRESSURES FOR WINDOW DOESN'T MATCH DESIGN
 PRESSURES SHOWN ON DOOR AND WINDOW SCHEDULE. REVISE AS
 REQUIRED.
 *****PROVIDE CALCULATIONS FORCALCULATED DESIGN
 PRESSURES AT ALL DOORS AND WINDOWS TO VERIFY COMPLIANCE
 WITH THE SPECIFIED BUILDING EXPOSURE C.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R301.
  
 E) REVISE DOOR BUCK DETAIL.2X4 PT WOOD BUCK IS NOT
 ADEQUATE TO PROVIDE FRAME FULL SUPPORT AS REQUIRED BY
 SEC. R613.6 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- SHEET A2:
 A) EXT. C.M.U. WALL SECTION:
 * SPECIFY WHEREIS THE INFORMATION FOR 7/16" O.S.B.
 ROOF SHEATHIHNG INFORMATION TAKEN FROM TO VERIFY
 COMPLIANCE WITH PROPOSED INSTALLATION AND SEC. R301 AND
 R803 OF 2004 FLORIDA RESIDENTIAL CODE.
 ** FOOTING DOESN'T MATCH FOOTING TYPE SHWON ON FOOTING
 SCHEDULE.
 *** ACCORDING TOTHIS DETAIL THE FOOTING IS 12" ABOVE
 GRADE AND 4" BELOWGRADE SINCE FOOTING SCHEDULE CALLS
 FOR 16" DEEP FOOTING.REVISE AS REQUIRED TO COMPLY
 WITH SEC. R403.1.4 OF 2004 FLORIDA RESIDENTAIL CODE.
 NEED TO SHOW MINIMUM FOOTING EMBEDMENT BELOW GRADE AND
 FOOTING ABOVE GRADE.
 **** SPECIFY R-VALUE FOR INSULATION SPECIFIED FOR THE
 WALL.
  
 B) COORDINATE WITH ZONING REGARDING CONSTRUCTION OF
 PRIVACY WALL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712