| Plan Review Notes For Permit 08020675 |
| Permit Number |
08020675 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-07 11:13:26 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED | | | | | | 1)PROVIDE BUCK FASTENING DETAILS. SPECIFY THE SPACING | | | AND EMBED DEPTH OF THE TAPCONS THAT WILL BE USED TO | | | ATTACH THE 2X WOOD BUCKS. | | | | | | 2) SUBMIT (2) TWO COPIES OF PRODUCT APPROVALS FOR STORM | | | PANELS THAT ARE REQUIRED FOR THE NEW FRENCH DOORS. FAC | | | RULE 9B-72 AND R301.2.1.2. | | | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | NEW FRENCH DOORS REQUIRE THE DOORS TO HAVE IMPACT | | | PROTECTION. SUBMIT (2) COPIES OF PRODUCT APPROVALS FOR | | | THE STORM PANELS THAT WILL BE INSTALLED. SPECIFY THE | | | MOUNT TYPE, FASTENER TYPE AND SPACING BY CIRCLING THE | | | ONES THAT WILL BE USED ON THE PRODUCT APPROVAL. | | | | | | 4)THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN IS REQUIRED ON THE DRAWINGS. FBC | | | 106.1.3* CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|