| Plan Review Notes For Permit 08020675 |
| Permit Number |
08020675 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-29 13:05:27 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED | | | | | | 1) THE SCOPE OF WORK ON THE APPLICATION STATES THAT THE | | | EXISTING BEDROOM WINDOW IS BEING REPLACED BY FRENCH | | | DOORS. SUBMIT STRUCTURAL DETAILS FOR THE OPENING. | | | SPECIFY THE EXISTING OPENING SIZE AND THE NEW OPENING | | | SIZE. IF CBS CONSTRUCTION SHOW LOCATION AND SIZE OF | | | STEEL REINFORCING, BLOCK LINTEL AND TIE BEAM. IF WOOD | | | FRAME SHOW HEADER SIZE, FRAMING DETAILS, HURRICANE | | | STRAPPING. | | | | | | 2)PROVIDE BUCK FASTENING DETAILS. | | | | | | 3) SUBMIT PRODUCT APPROVALS FOR STORM PANELS THAT ARE | | | REQUIRED FOR THE NEW FRENCH DOORS. FAC RULE 9B-72 AND | | | R301.2.1.2. | | | | | | 4) THE VALUE OF THE WORK ($200) IS TOO LOW. THE VALUE | | | IS TO INCLUDE THE COST OF MATERIALS AND LABOR AS WOULD | | | BE CHARGED BY A CONTRACTOR. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|