Plan Review Notes
Plan Review Notes For Permit 08020670
Permit Number 08020670
Review Stop B
Sequence Number 2
Notes
Date Text
2008-04-01 12:08:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3, AREA PER OCCUPANCY,
 OCCUPANT LOAD.
  
 AT A MINIMUM, PLEASE PROVIDE INFORMATION REGARDING USE
 OF SPACE ON EACH FLOOR AND TOTAL SQUARE FOOT AREA FOR
 EACH FLOOR.USE IS TO BE SPECIFIC; ARE ALL OF THESE
 ROOMS CLASSROOMS, WHAT AGE ARE THE STUDENTS?SPRINKLER
 INFORMATION REQUIRED.IF THE CORRIDORS ARE FIRE RATED,
 IT IS POSSIBLE THAT ONLY FIRE RATED DOORS ARE
 PERMITTED.PRIOR TO A REVIEW, ALL INFORMATION
 REQUESTED MUST BE PROVIDED TO DETERMINE CODE
 REQUIREMENTS OR ENOUGH INFORMATION FOR ME TO DISCERN
 THE ABOVE INFORMATION.
  
 3.PROVIDE DIMENSIONS OF CORRIDORS.
  
 YOU CANNOT REDUCE THE MEANS OF EGRESS WITH DOOR SWING
 BY MORE THAN HALF.DIMENSION OF DOORS, OCCUPANT LOAD,
 AND CORRIDOR DIMENSION REQUIRED.FBC1005.4.
  
 4.THE PROPOSED EGRESS DOORS ARE OBSTRUCTED BY OTHER
 DOORS.SEE FBC1003.6.
  
 5.SEE FBC1004.1 .NOTE THAT YOU PROPOSE TO REDUCE
 THE CLEAR WIDTH OF A COMPONENT OF MEANS OF EGRESS. CODE
 COMPLIANCE MUST BE DEMONSTRATED.
  
 PLEASE PROVIDE DOOR DIMENSIONS.THEY ARE SHOWN
 GRAPHICALLY ON THE PLAN AS MUCH SMALLER THAN OTHER
 DOORS.ONLY ONE DIMENSION IS PROVIDED.IS THIS THE
 DOOR DIMENSION, OR THE CORRIDOR DIMENSION?
  