| 2008-04-11 11:00:39 | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08020666 |
| | ADD: 1335 OLD OKEECHOBEE RD |
| | CONT: MAURO BROTHERS LLC |
| | TEL: (561)738-4713 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-11-08 |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | **THIS INFORMATION SHALL BE SHOWN ON PLANS.** |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)OK |
| | 5)OK |
| | |
| | 6)CLEARLY INDICATE THE TOTAL SQUARE FOOT OF THE AREA |
| | WHERE THE MEZZANINE WILL BE CONSTRUCTED, AND SHOW THE |
| | ENTIRE FLOOR PLAN ON THE STRUCTURAL DRAWINGS. THE |
| | BUILDING TYPE SHALL BE INDICATED ON THE DRAWINGS PER |
| | TABLE 601. |
| | |
| | **THE 8X11 SHEET ATTACHED TO THE DRAWINGS SHOWS THE |
| | AREA OF THE MEZZANINE HOWEVER, THE TOTAL SQUARE FOOT OF |
| | THE SUITE IS NOT INDICATED AS REQUESTED AND THE ENTIRE |
| | FLOOR PLAN IS NOT SHOWN. ARE THERE ANY OFFICES BELOW |
| | THE MEZZANINE? IF SO PLEASE SHOW THE FLOOR PLAN FOR THE |
| | OFFICE AREA AND ELEVATION DRAWINGS OF THE OFFICES. WHAT |
| | IS THE FIRE RATING OF THE PARTITION WALLS SEPARATING |
| | EACH SUITE? ** |
| | |
| | **THE BUILDING TYPE NOTED ON THE PLANS IS TYPE 1. TYPE |
| | 1 BUILDINGS ARE CONSTRUCTED WITH NONCOMBUSTIBLE |
| | MATERIALS. FBC 602.2 AND TABLE 601. SEE SECTION 603 |
| | WHERE FIRE-RETARDANT- TREATED WOOD IS PERMITTED IN SOME |
| | SITUATIONS. STATE THE HEIGHT OF THE BUILDING ON THE |
| | PLANS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | FAX (561)805-6676 |