| Date |
Text |
| 2008-03-10 15:08:32 | *****DENIED***** |
| | |
| | |
| | 1.THE CORRECT ADDRESS, INCLUDING THE SUITE NUMBER, |
| | SHALL BE LISTED IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET.PLEASE BE ADVISED OF THE FOLLOWING:(A) |
| | SUITE 200 IS SHOWN ON PLAN SHEET FP-1 INSTEAD OF SUITE |
| | 600(B) THE JOB SITE ADDRESS IS IN WEST PALM BEACH AND |
| | NOT PALM BEACH AS LISTED IN THE TITLE BLOCK ON SHEETS |
| | E-1 AND E-2. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 4.PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED |
| | DURING THE SCOPE OF WORK.IF SO, MEANS OF EGRESS AND |
| | AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN |
| | PLACE AND CONTINUOUSLY MAINTAINED. |
| | |
| | 5.PLEASE LIST THE FOLLOWING FOR THE BUILDING: |
| | OCCUPANCY TYPE,OCCUPANT LOAD,FIRE ALARM AND/OR FIRE |
| | SPRINKLER DEVICES, AND ANY OTHER PERTINENT |
| | INFORMATION. |
| | |
| | 6.PLEASE PROVIDE A CLEAR REPRENSENTATION OF THE |
| | MEZZANINE IN RELATION TO THE FLOOR PLAN INCLUDING EXIT |
| | LIGHTS/DOORS, EMERGENCY LIGHTS, ETC. |
| | |
| | 7.HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE |
| | ALARM DEVICES, IF SO EQUIPPED.IN ADDITION. HOW WILL |
| | FIRE SPRINKLER PROTECTION UNDERNEATH THE MEZZANINE BE |
| | ACHIEVED? |
| | |
| | 8.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |