| 2008-02-28 11:57:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION |
| | AND OCCUPANCY LOAD ON THE PLANS. |
| | PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR |
| | PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT |
| | TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED |
| | BELOW. |
| | |
| | A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3, |
| | AND A-5 |
| | |
| | B} BUSSINESS (SEE SECTION 304): GROUP B |
| | |
| | C} EDUCATIONAL (SEE SECTION 305): GROUP E |
| | |
| | D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS |
| | F-1 AND F-2 |
| | |
| | E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3, |
| | H-4, AND H-5 |
| | |
| | F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, |
| | AND I-3 |
| | |
| | G} MERCANTILE (SEE SECTION 309): GROUP M |
| | |
| | H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3 |
| | AS APPLICABLE IN SECTION 101.2, AND R-4 |
| | |
| | I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2 |
| | |
| | J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP |
| | U |
| | |
| | K} DAY CARE (SEE SECTION 313): GROUP D |
| | |
| | **IT APPEARS THAT THIS IS A BUSSINESS. IF THIS IS A |
| | BUSSINESS MINIMUM REQUIRED PLUMBING FIXTURES REQUIRED |
| | ARE AS FOLLOWS PER FBC PLUMBING TABLE 403.1. 1 WATER |
| | CLOSET, 1 LAVATORY, AND ONE DRINKING FOUNTAIN. THE |
| | FLOOR PLAN IS NOT INDICATING AN EXISTING DRINKING |
| | FOUNTAIN. A DRINKING FOUNTAIN IS REQUIRED AND SHALL BE |
| | ACCESSIBLE PER CHAPTER 11 FLORIDA ACCESSIBILITY CODE |
| | THE FOLLOWING SECTIONS |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| | CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| | 2007 REVISIONS" |
| | |
| | 3. CLEARLY INDICATE THE ADDRESS ON ALL RESUBMITTED |
| | PLAN SHEETS. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4.NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | 5. THE PROPOSED DOUBLE SHAMMPOO SINK CAN NOT TIE INTO |
| | THE EXISTING WET VENT OF THE BATHROOM. PER FBC-2004, |
| | PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | 6. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| | PLUMBING PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC |
| | RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND |
| | SIZES WITH CLEANOUT LOCATIONS OF THE PROPOSED DOUBLE |
| | SHAMPOO SINK. |
| | |
| | 7. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| | PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS |
| | REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND |
| | COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS, |
| | LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW |
| | PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE |
| | WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER |
| | ARRESTORS (IF APPLICABLE) WHERE QUICK CLOSING VALVES |
| | ARE UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, |
| | ICE MAKERS) **604.9. |
| | |
| | 8. THE PROPOSED NEW 50 GAL. WATER HEATER BEING LOCATED |
| | IN THE BATHROOM APPEARS TO INFRINGE INTO THE REQUIRED |
| | CLEAR FLOOR SPACE OF THE REQUIRED ACCESSIBLE LAVATORY. |
| | PER FBC CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION |
| | 11-4.19.3 LAVATORY CLEARANCE 30" X 48" & SHALL EXTEND |
| | MAXIMUM 19" UNDER LAV. PROVIDE A MINIMUM 1/8 INCH SCALE |
| | FLOOR PLAN LAYOUT OF THIS BUILDING WITH THE BATHROOM |
| | LAYOUT. INCLUDE FIXTURE SPACEING AND WATER HEATER |
| | LOCATION ON THE FLOOR PLAN. CLEARLY INDICATE THE CLEAR |
| | FLOOR SPACE OF THE LAVATORY PER 11-4.19.3 ON THIS FLOOR |
| | PLAN. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION |
| | 106.1.3 QUALITY OF BUILDING PLANS. |
| | |
| | 9. THE VALUE ON THE PERMIT APPLICATION SEEMS TO LOW. |
| | PER FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | **PROVIDE COPY OF SIGNED CONTRACT BY BOTH OWNER AND |
| | CONTRACTOR OF PROPOSED WORK WITH THE TOTAL VALUE |
| | INCLUDING ALL LABOR, MATERIALS, WATER HEATER, DOUBLE |
| | BOWL SHAMPOO SINK. |
| | |
| | 10. THE PERMIT APPLICATION IS INCOMPLETE, THE OWNER OF |
| | RECORD NEEDS TO BE FILLED OUT AND THE PLUMBING |
| | CONTRACTOR'S STATE LICENSE NUMBER NEEDS TO BE |
| | INDICATED. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, |
| | SECTION 105 PERMITS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |