2008-07-01 08:52:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 2ND REVIEW - SHEET S3, SHOWING LOCATION OF
 IMPROVEMENTS, IS PREPARED BY AN ENGINEER BUT NOT
 SIGNED, SEALED, AND DATED.THE PERMIT IS TO CLEARLY
 SHOW SCOPE OF WORK; THEREFORE A LOCATION PLAN IS
 REQUIRED.THIS SHOULD BE DONE BY THE DESIGNER OF
 RECORD OR DELEGATED ENGINEER.IF DONE BY A DELEGATED
 ENGINEER, IT SHOULD BE REVIEWED BY ENGINEER OF RECORD.
  
 IT IS NOT CLEAR WHICH OF THE MECHANICAL ROOMS ARE TO BE
 INCLUDED IN THIS PERMIT.S3 IS A ROOF FRAMING PLAN
 SHOWING THE FRAMING FOR THE ENTIRE ROOF.PLEASE
 CLARIFY SCOPE OF WORK ON THE PLAN.
  
 3RD REVIEW - SAME ROOF PLAN SUBMITTED.PROVIDE AN
 OVERALL ROOF PLAN WHICH CLEARLY SHOWS LOCATION OF
 PROPOSED REPAIRS.DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS FS471, FS481.
  
 2.ADDRESSED.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.
  
 2ND REVIEW - PRODUCT APPROVALS WERE NOT SUBMITTED.
 THIS IS REQUIRED FOR ALL COMPONENTS AND CLADDING, WHICH
 WOULD INCLUDE WALL PANELS, ROOF COMPONENTS & CLADDING
 (ROOF COVER, NOT DECK UNLESS THE DECK IS ALSO ACTING AS
 ROOF COVER), LOUVERS IF NEW LOUVERS ARE INSTALLED.
  
 3RD REVIEW - SOMEONE WROTE "TOWN & COUNTY 5 RIB ROOF
 PANELS SEE ATTTACHED PROD APPROVAL" ON A PHOTOCOPY OF A
 PORTION OF THE ROOF PLAN.NO PRODUCT APPROVALS WERE
 SUBMITTED.PLEASE PRINT THE PRODUCT APPROVAL ALONG
 WITH ALL ASSOCIATED DOCUMENTS (EVALUATION REPORT,
 INSTALLATION INSTRUCTIONS) FROM THE WEBSITE
 WWW.FLORIDABUILDING.ORG.THE ENGINEER IS TO REVIEW THE
 PRODUCT APPROVALS, FBC*106.3.3 (SHOP DRAWING REVIEW
 STAMP OR LETTER OR INCORPORATE REFERENCE INTO SIGNED
 AND SEALED PLAN).
  
 4-6. ADDRESSED.
  
 7. THE ORIGINAL PERMIT PACKAGE WAS NOT SUBMITTED.OLD
 SHEETS ARE TO BE SUBMITTED FOR REFERENCE, AND THE
 PERMIT APPLICATION IS REQUIRED FOR PERMIT ISSUANCE.
  
 3RD REVIEW, THE ORIGINAL PERMIT PACKAGE WAS NOT
 SUBMITTED.WHEN RESUBMITTING, PICK UP THE ORIGINAL
 PERMIT PACKAGE FROM THE FRONT DESK.PROVIDE TWO
 IDENTICAL, COLLATED SETS OF PERMIT DOCUMENTS.OLD
 SHEETS ARE TO BE MARKED "VOID" AND SUBMITTED FOR
 REFERENCE.THIS WAS DONE FOR THIS REVIEW AS A
 COURTESY, BUT DUE TO WORK LOAD WE ARE UNABLE TO DO THIS
 FOR EVERY PERMIT.
  
 8.ADDRESSED.
  
 9.EXISTING CONDITIONS NOT CLEAR.SEE ENGINEERING
 CALCS SHEET 3 AND ROOF FRAMING PLAN SHEET S3 (PREPARED
 BY DE BRITT & ASSOCIATES ENGINEERS).IT APPEARS THAT
 ADDITIONAL FRAMING MEMBERS WERE ADDED GRAPHICALLY.THE
 ALTERED PLAN SHOWS ROOF BEAMS WHICH ARE CONSISTENT WITH
 SHEET 3 OF CALCS.SHEET 3 STATES THAT 9.75' SPAN DOES
 NOT WORK FOR COMPONENT & CLADDING WIND PRESSURES, AND
 NEW DECK SPAN IS 4.8'.THE EXISTING PLAN APPEARS TO
 SHOW ONE ROOF FRAMING MEMBER IN THE CENTER, WHICH DOES
 NOT APPEAR ON THE NEW PLAN.DOES THIS GET REMOVED? SEE
 SHEET S1 PREPARED BY PBSJ, WHICH STATES "3ALL STEEL
 BEAMS ARE EXISTING".IT IS NOT CLEAR WHY S1 SHOWS THE
 ROOF FRAMING AS EXISTING AND NO CHANGES TO BE DONE, BUT
 THE CALCS SHEET 03 SHOW THAT A TOTAL OF 8 ROOF JOISTS
 ARE TO BE INSTALLED (EXISTING FRAMING HAS ONLY 3).IT
 IS NOT CLEAR WHY THE CALCS WOULD INDICATE THAT
 ADDITIONAL REINFORCEMENT IS NEEDED, BUT THE PLAN (WHICH
 IS WHAT THE CONTRACTOR AND INSPECTOR WILL USE TO DO THE
 WORK) DO NOT SHOW THIS REINFORCEMENT.
  
 3RD REVIEW, NOT ADDRESSED.PLANS SHOW ROOF PANELS OVER
 EXISTING, BUT CALCS STATE THAT EXISTING SPAN DOES NOT
 WORK.PLEASE SEE CALCULATIONS.SEE ALSO FBC EB
 407.1.2, FBC EB 507.2.IT IS NOT CLEAR IF DESIGNER HAS
 DETERMINED THIS TO BE A REPAIR OR LEVEL 1 ALTERATION,
 BUT BASED ON CALCULATIONS PROVIDED IT APPEARS THAT
 ADDITIONAL STRUCTURAL WORK MUST BE DONE.PLEASE
 CLARIFY.
  
 10-11. ADDRESSED.
  