2008-04-18 09:09:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 SHEET S3, SHOWING LOCATION OF IMPROVEMENTS, IS PREPARED
 BY AN ENGINEER BUT NOT SIGNED, SEALED, AND DATED.THE
 PERMIT IS TO CLEARLY SHOW SCOPE OF WORK; THEREFORE A
 LOCATION PLAN IS REQUIRED.THIS SHOULD BE DONE BY THE
 DESIGNER OF RECORD OR DELEGATED ENGINEER.IF DONE BY A
 DELEGATED ENGINEER, IT SHOULD BE REVIEWED BY ENGINEER
 OF RECORD.
  
 IT IS NOT CLEAR WHICH OF THE MECHANICAL ROOMS ARE TO BE
 INCLUDED IN THIS PERMIT.S3 IS A ROOF FRAMING PLAN
 SHOWING THE FRAMING FOR THE ENTIRE ROOF.PLEASE
 CLARIFY SCOPE OF WORK ON THE PLAN.
  
 2.ADDRESSED.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.
  
 PRODUCT APPROVALS WERE NOT SUBMITTED.THIS IS REQUIRED
 FOR ALL COMPONENTS AND CLADDING, WHICH WOULD INCLUDE
 WALL PANELS, ROOF COMPONENTS & CLADDING (ROOF COVER,
 NOT DECK UNLESS THE DECK IS ALSO ACTING AS ROOF COVER),
 LOUVERS IF NEW LOUVERS ARE INSTALLED.
  
 4-6. ADDRESSED.
  
 NEW COMMENTS:
  
 7. THE ORIGINAL PERMIT PACKAGE WAS NOT SUBMITTED.OLD
 SHEETS ARE TO BE SUBMITTED FOR REFERENCE, AND THE
 PERMIT APPLICATION IS REQUIRED FOR PERMIT ISSUANCE.
  
 8.THE SCOPE OF WORK HAS CHANGED FROM ORIGINAL
 APPLICATION.THE WORK AS SHOWN IS NOT WITHIN THE SCOPE
 OF A SHEET METAL CONTRACTOR LICENSE, LIGHT GAGE METAL
 ONLY, FS489.A ROOF PERMIT AND A STRUCTURAL PERMIT
 WILL BE REQUIRED.
  
 9.EXISTING CONDITIONS NOT CLEAR.SEE ENGINEERING
 CALCS SHEET 3 AND ROOF FRAMING PLAN SHEET S3 (PREPARED
 BY DE BRITT & ASSOCIATES ENGINEERS).IT APPEARS THAT
 ADDITIONAL FRAMING MEMBERS WERE ADDED GRAPHICALLY.THE
 ALTERED PLAN SHOWS ROOF BEAMS WHICH ARE CONSISTENT WITH
 SHEET 3 OF CALCS.SHEET 3 STATES THAT 9.75' SPAN DOES
 NOT WORK FOR COMPONENT & CLADDING WIND PRESSURES, AND
 NEW DECK SPAN IS 4.8'.THE EXISTING PLAN APPEARS TO
 SHOW ONE ROOF FRAMING MEMBER IN THE CENTER, WHICH DOES
 NOT APPEAR ON THE NEW PLAN.DOES THIS GET REMOVED? SEE
 SHEET S1 PREPARED BY PBSJ, WHICH STATES "3ALL STEEL
 BEAMS ARE EXISTING".IT IS NOT CLEAR WHY S1 SHOWS THE
 ROOF FRAMING AS EXISTING AND NO CHANGES TO BE DONE, BUT
 THE CALCS SHEET 03 SHOW THAT A TOTAL OF 8 ROOF JOISTS
 ARE TO BE INSTALLED (EXISTING FRAMING HAS ONLY 3).IT
 IS NOT CLEAR WHY THE CALCS WOULD INDICATE THAT
 ADDITIONAL REINFORCEMENT IS NEEDED, BUT THE PLAN (WHICH
 IS WHAT THE CONTRACTOR AND INSPECTOR WILL USE TO DO THE
 WORK) DO NOT SHOW THIS REINFORCEMENT.
  
 10.PLEASE REMOVE HVHZ FROM DESIGN CRITERIA.IN THE
 PAST THERE HAVE BEEN SOME SIGNIFICANT DESIGN
 DIFFERENCES IN HVHZ, AND SOME HAVE NOT BEEN MORE
 STRINGENT (FOR INSTANCE, A STRESS INCREASE FOR STEEL
 WHICH WAS NEVER PERMITTED IN FBC2001 OR 2004).
 THEREFORE, DESIGN IS TO BE DONE TO FBC2004 MINIMUM.
  
 11.PT WOOD NAILERS ARE SHOWN.PROVIDE ENOUGH
 INFORMATION ABOUT THIS BUILDING TO SHOW THAT
 COMBUSTIBLES ARE PERMITTED.IF THIS IS A TYPE I OR II
 BUILDING, THIS DOES NOT APPEAR TO BE PERMITTED IN
 FBC603.1.IF THIS IS NOT A TYPE I OR II BUILDING,
 PROVIDE A CODE SUMMARY (BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY
 CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY) TO SHOW
 THAT COMBUSTIBLES CAN BE USED.
  
  
  