2008-03-07 16:44:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE PRODUCT APPROVAL, SHEET 7.YOU'VE HIGHLIGHTED
 A ROW, BUT THIS IS NOT THE CORRECT ROW.THIS IS FOR
 CRETE FLEX, PRESSURE OF LESS THAN 30PSF.YOU ARE
 DESIGNING TO 47.2PSF, SO MUST USE THE NEX SECTION.
 MASONRY SUBSTRATE, SPAN OVER 5', TAPCON, REQUIRES 7"
 SPACING RATHER THAN THE 9" SPECIFIED.