| 2008-04-01 09:01:42 | ** DENIED** |
| | |
| | |
| | 1) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF COMPLETING. |
| | PLEASE SEE THAT ALL CIRCUITING NEEDS TO BE COMPLETE AND |
| | COORDINATE WITH THE PANEL SCHEDULES SUBMITTED OR TO BE |
| | SUBMITTED. |
| | FOR EXAMPLE: PLEASE SEE PLANS NOTE CIRCUIT 34 ON PANEL |
| | PH, YET NO PANEL PH WAS SUBMITTED. |
| | PLEASE SEE SHEET E2.1.2, THIS SHEET ALSO NOTES THE SAME |
| | *D* FIXTURES TO BE CONTINUED ON E2.1.1, HOWEVER WHEN |
| | YOU LOOK AT THE OTHER SHEET THE *D* FIXTURES ARE ON |
| | PANEL PH-2. PLEASE SEE THE LOAD ON THIS CIRCUIT IS |
| | SHOWN HIGHER THAN THE LOAD FOR THE THREE *D* FIXTURES |
| | SHOWN. |
| | PLEASE SEE THE FIXTURES WHICH ARE NOTED TO GO TO |
| | EXISTING EMERGENCY CIRCUIT DOES NOT INCLUDE LOAD, |
| | CIRCUIT, PANEL, LOCATION ETC? |
| | |
| | 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND. FOR EXAMPLE: |
| | FIXTURE *B* WHICH DOES NOT SHOW ANY WATTAGE FOR BULB TO |
| | BE USED. LOAD CAN NOT BE DETERMINED FOR THIS CIRCUIT. |
| | ALMOST ALL LIGHTING IN DRIVE-THRU AREA IS SHOWN ON ONE |
| | CIRCUIT AND WITH OUT THIS INFORMATION THE CIRCUIT |
| | SIZING CAN NOT BE DETERMINED. |
| | THIS FIXTURE WAS LOOKED UP ON THE COMPANY?S WEB-SITE |
| | AND THIS FIXTURE HAS A WIDE RANGE OF WATTAGE. IF USING |
| | SOME OF THE HIGHER WATTAGE OF BULBS, THIS WOULD OVER |
| | LOAD THE CIRCUIT. |
| | PLEASE COMPLETE. |
| | NEC 220, 240.4, 310.16, ETC |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE COMPLETE THE LOCATIONS OF NEW |
| | EQUIPMENT. PLEASE SEE THE ELECTRICAL ROOM AS SHOWN |
| | SHOWS TWO -2 TRANSFORMERS AND BOTH ARE SHOWN AS |
| | EXISTING. PLEASE ALSO SEE OTHER EQUIPMENT ON PLANS ALSO |
| | SHOWS OTHER EQUIPMENT AS EXISTING ALSO. |
| | PLEASE CLEARLY LABEL ALL EQUIPMENT AND SHOW LOCATIONS. |
| | 110.26, 240.24, ETC |
| | FBC 106.1.2 |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |