| Plan Review Notes For Permit 08020633 |
| Permit Number |
08020633 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-03-18 14:14:46 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | | THE FOLLOWING: | | | | | | THIS COMMENT WAS FROM THE PREVIOUS TWO REVIEWS, AND NOT | | | ADDRESSED: | | | | | | 2/29/08 REVIEW: 1} THE RISER DIAGRAM ON SHEET A-2 | | | INDICATES "EXISTING", BUT NOTES PERTAINING TO THE RISER | | | INDICATE LOCATION OF THE METER TO BE UNKNOWN. CLARIFY | | | TO INDICATE IF EXISTING OR TO BE INSTALLED, ALSO LOCATE | | | THE SERVICE EQUIPMENT ON THE PLAN. 3/11/08 REVIEW: * | | | THIS COMMENT WAS OVERLOOKED. PLEASE LOCATE ALL SERVICE | | | EQUIPMENT IN THE FLOOR PLAN, A-1..** 3/18/08 REVIEW- | | | THE METER AND DISCONNECT SHOWN ON THE RISER STILL HAVE | | | NOT BEEN LOCATED ON THE PLAN. NOW ON THIS PLAN THE THE | | | PANEL IS SHOWN AS "EXISTING", THE WALL IT'S SHOWN IN IS | | | A NEW WALL, OBVIOUSLY THE PANEL CANNOT BE IN THAT | | | LOCATION. THE PERSON TAKING RESPONSIBILITY FOR THIS | | | PLAN SHOULD VISIT THE SITE TO DETERMINE THESE | | | LOCATIONS. | | | | | | NEW COMMENT : | | | | | | 2} THE LOCATION SHOWN FOR THE PANEL IS IN VIOLATION OF | | | THE CLEARANCE REQUIREMENTS OF 110.26, 2005 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|