Plan Review Notes
Plan Review Notes For Permit 08020633
Permit Number 08020633
Review Stop E
Sequence Number 3
Notes
Date Text
2008-03-18 14:14:46 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 THIS COMMENT WAS FROM THE PREVIOUS TWO REVIEWS, AND NOT
 ADDRESSED:
  
 2/29/08 REVIEW: 1} THE RISER DIAGRAM ON SHEET A-2
 INDICATES "EXISTING", BUT NOTES PERTAINING TO THE RISER
 INDICATE LOCATION OF THE METER TO BE UNKNOWN. CLARIFY
 TO INDICATE IF EXISTING OR TO BE INSTALLED, ALSO LOCATE
 THE SERVICE EQUIPMENT ON THE PLAN. 3/11/08 REVIEW: *
 THIS COMMENT WAS OVERLOOKED. PLEASE LOCATE ALL SERVICE
 EQUIPMENT IN THE FLOOR PLAN, A-1..** 3/18/08 REVIEW-
 THE METER AND DISCONNECT SHOWN ON THE RISER STILL HAVE
 NOT BEEN LOCATED ON THE PLAN. NOW ON THIS PLAN THE THE
 PANEL IS SHOWN AS "EXISTING", THE WALL IT'S SHOWN IN IS
 A NEW WALL, OBVIOUSLY THE PANEL CANNOT BE IN THAT
 LOCATION. THE PERSON TAKING RESPONSIBILITY FOR THIS
 PLAN SHOULD VISIT THE SITE TO DETERMINE THESE
 LOCATIONS.
  
 NEW COMMENT :
  
 2} THE LOCATION SHOWN FOR THE PANEL IS IN VIOLATION OF
 THE CLEARANCE REQUIREMENTS OF 110.26, 2005 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718