 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 THIS COMMENT WAS FROM THE PREVIOUS REVIEW, AND NOT
 ADDRESSED:
  
 1} THE RISER DIAGRAM ON SHEET A-2 INDICATES "EXISTING",
 BUT NOTES PERTAINING TO THE RISER INDICATE LOCATION OF
 THE METER TO BE UNKNOWN. CLARIFY TO INDICATE IF
 EXISTING OR TO BE INSTALLED, ALSO LOCATE THE SERVICE
 EQUIPMENT ON THE PLAN* THIS COMMENT WAS OVERLOOKED.
 PLEASE LOCATE ALL SERVICE EQUIPMENT IN THE FLOOR PLAN,
 A-1..
  
 2} THE RESUBMITTAL NOW INDICATES A 150 AMP RATED PANEL
 WITH A 200 AMP MAIN BREAKER. THE RISER. SEE 408.36
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER