| Plan Review Notes For Permit 08020633 |
| Permit Number |
08020633 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-11 15:56:58 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | | THE FOLLOWING: | | | | | | THIS COMMENT WAS FROM THE PREVIOUS REVIEW, AND NOT | | | ADDRESSED: | | | | | | 1} THE RISER DIAGRAM ON SHEET A-2 INDICATES "EXISTING", | | | BUT NOTES PERTAINING TO THE RISER INDICATE LOCATION OF | | | THE METER TO BE UNKNOWN. CLARIFY TO INDICATE IF | | | EXISTING OR TO BE INSTALLED, ALSO LOCATE THE SERVICE | | | EQUIPMENT ON THE PLAN* THIS COMMENT WAS OVERLOOKED. | | | PLEASE LOCATE ALL SERVICE EQUIPMENT IN THE FLOOR PLAN, | | | A-1.. | | | | | | 2} THE RESUBMITTAL NOW INDICATES A 150 AMP RATED PANEL | | | WITH A 200 AMP MAIN BREAKER. THE RISER. SEE 408.36 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|