| 2008-03-10 10:52:37 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATIONS AND ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A COPY OF THE RECORDED NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT A SURVEY/SITE PLAN SPECIFYING THE DISTANCES |
| | OF THE ADDITION TO PROPERTY LINES. |
| | |
| | 4) IF LESS THAN 6 FEET TO THE PROPERTY LINES, THE SITE |
| | PLAN WILL NEED TO SPECIFY THAT THE DISTANCE TO ANY |
| | STRUCTURES ON THE ADJACENT PROPERTY IS MORE THAN 6 FEET |
| | OR SHOW COMPLIANCE WITH R302.1 AND R302.2. R302.1 |
| | EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| | SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| | RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| | NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| | AN ADJACENT PROJECTION OR WALL. R302.2 OPENINGS SHALL |
| | NOT BE PERMITTED IN THE EXTERIOR WALL OF A DWELLING OR |
| | ACCESSORY BUILDING THAT IS SEPARATED FROM AN ADJACENT |
| | BUILDING BY A DISTANCE OF LESS THAN 6 FEET (1828 MM). |
| | THIS DISTANCE SHALL BE MEASURED PERPENDICULAR TO THE |
| | LINE USED TO DETERMINE THE SEPARATION DISTANCE. |
| | |
| | 5) THE DESIGN DATA ON SHEET 1 INCORRECTLY SPECIFIES |
| | ASCE 7-98. THE EDITION REFERENCED BY THE 2004 FBC IS |
| | ASCE 7-02. PLEASE CORRECT. |
| | |
| | 6) THE ROOF PITCH ON SHEET 1 SPECIFIES A FLAT ROOF AND |
| | THE PLANS INDICATE A SLOPED ROOF. SPECIFY THE ROOF |
| | SLOPE ON THE PLANS. FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 7) SPECIFY THE REQUIRED SOIL BEARING CAPACITY OF THE |
| | SOIL ON THE PLANS. FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 8) REVISE THE ROOF SHEATHING FASTENING NOTES ON THE |
| | TYPICAL WALL SECTION ON SHEET 5 TO COMPLY WITH |
| | R803.2.3.1 WHICH REQUIRES 8D RING-SHANK NAILS. |
| | |
| | 9) SUBMIT TWO (2) COPIES OF THE PRODUCT APPROVALS |
| | REQUIRED BY DCA RULE 9B-72. FBC 106.1* CITY |
| | AMENDMENTS. |
| | |
| | 10) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW |
| | MULLIONS. DCA RULE 9B-72. |
| | |
| | 11)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. |
| | THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 12) THE PRESSURES SPECIFIED IN THE NOA FOR THE SINGLE |
| | HUNG WINDOWS WITH DSB ANNEALED GLASS ARE TOO LOW FOR |
| | THE SH34 WINDOWS. ONE OF THE OTHER TYPE OF GLAZING |
| | LISTED IN THE CHART ON PAGE 1 OF THE NOA MUST BE USED. |
| | |
| | 13)SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE, |
| | FASTENER TYPE AND SPACING, EDGE DISTANCE, GLASS |
| | SEPARATION, ETC. SEE SAMPLE OF SCHEDULE ATTACHED. FBC |
| | 106.1.1* CITY AMENDMENTS. |
| | |
| | 14) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | CALCULATION FORMS. SUBMIT TWO COPIES OF ENERGY CALCS. |
| | FBC 13-600. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |