Plan Review Notes
Plan Review Notes For Permit 08020617
Permit Number 08020617
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-31 10:42:25*****PROVISO*****
  
 1.NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE
 REQUIRED EXIT STAIRTOWERS.PLEASE PROVIDE A NOTE ON
 THE PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY
 EXIT STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY.
  
 2.ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR
 DEVICES.
  
 3.ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT
 INTERFERE ANY STANDPIPE ROOF MANIFOLDS.
  
 4.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK
 TO COMPLY WITH NFPA 241.
  
  
 (PLAN SHEET C4.1 STAMPED, INITIALED, AND DATED)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW