| Plan Review Notes For Permit 08020593 |
| Permit Number |
08020593 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-04 08:36:32 | DENIED; | | | 1. PAGE P1, DWV RISER; NO DEAD ENDS PERMITED IN THE | | | SANITARY DRAINAGE SYSTEM LONGER THAN 2'. FBC-PLUMBING | | | SECTION 704.5. | | | 2. PAGE A1.0 CLEAR FLOOR UNDER BREAK SINK TO COMPLY | | | WITH FBC-BUILDING SECTION 11-4.24.5 THE CLEAR FLOOR | | | SPACE SHALL EXTEND 19" UNDER THE SINK. | | | 3. PAGE A7.0 DETAIL 3; NO DOORS OR BASE PERMITED IN | | | FRONT OF BREAK ROOM SINK. SEE SECTION 11-4.24.3 KNEE | | | CLEARANCE 19"DEEP SHALL BE PROVIDED UNDERNEATH THE | | | SINK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|