Plan Review Notes
Plan Review Notes For Permit 08020593
Permit Number 08020593
Review Stop P
Sequence Number 2
Notes
Date Text
2008-04-04 08:36:32DENIED;
 1. PAGE P1, DWV RISER; NO DEAD ENDS PERMITED IN THE
 SANITARY DRAINAGE SYSTEM LONGER THAN 2'. FBC-PLUMBING
 SECTION 704.5.
 2. PAGE A1.0 CLEAR FLOOR UNDER BREAK SINK TO COMPLY
 WITH FBC-BUILDING SECTION 11-4.24.5 THE CLEAR FLOOR
 SPACE SHALL EXTEND 19" UNDER THE SINK.
 3. PAGE A7.0 DETAIL 3; NO DOORS OR BASE PERMITED IN
 FRONT OF BREAK ROOM SINK. SEE SECTION 11-4.24.3 KNEE
 CLEARANCE 19"DEEP SHALL BE PROVIDED UNDERNEATH THE
 SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  