2008-02-29 10:04:40DENIED;
 1. WATER RISER DIAGRAM; WATER HAMMER ARRESTOR IS
 REQUIRED AT BREAKICE BOX SEE FBC PLUMBING SECTION
 604.9. SPEC OUT SIZE AND MANUFACTURE ON PLANS.
 2. CONDENSATE FROM COMPUTER A/C TO DISCHARGE TO THE
 OUTSIDE, STORM DRAINS OR TO CONDENSATE DRAINS. NOT
 PERMITED TO GO TO SANITARY. WEST PALM BEACH UTILITY
 ORD.
 3. BREAK SINK TO MEET ACCESSIBILITY CODE CHAPTER 11 OF
 THE FBC BUILDING CODE. SEE SECTIONS 11-4.24.1 THRU
 11-4.24.7. SHOW THE FRONTAL CLEAR FLOOR SPACE ON FLOOR
 PLANS .