| Notes |
| Date |
Text |
| 2008-02-29 15:52:30 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE WHAT THE PRIMARY OCP IS FOR TRANSFORMER | | | "TLM". IF THE 60 AMP RATED DISCONNECT HAS IN FACT A 60 | | | AMP OCP INSTALLED, IT WOULD NOT COMPLY WITH 450.3(B). | | | 125% OF A 30000 WATT TRANSFORMER WOULD ALLOW A 50 AMP | | | OCP MAXIMUM. | | | | | | 2} THERE IS NO SECONDARY OCP FOR "TLM" AS PANEL "LM" IS | | | LISTED AS MAIN LUG ONLY. SEE 408.36 AND 450.3(B). | | | | | | 3} THE LIGHTING CIRCUITS ARE NOT ON THE PANEL SCHEDULE | | | AND DO NOT APPEAR TO BE CALCULATED AT 125% (CONTINUOUS | | | LOAD) PER 215.2. | | | | | | 4} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | | FAC. THE DATE IS MISSING. | | | | | | 5} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL | | | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER PER | | | 61G15-23.002FLORIDA ADMINISTRATIVE CODE.. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|