Plan Review Notes
Plan Review Notes For Permit 08020593
Permit Number 08020593
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-29 15:52:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE WHAT THE PRIMARY OCP IS FOR TRANSFORMER
 "TLM". IF THE 60 AMP RATED DISCONNECT HAS IN FACT A 60
 AMP OCP INSTALLED, IT WOULD NOT COMPLY WITH 450.3(B).
 125% OF A 30000 WATT TRANSFORMER WOULD ALLOW A 50 AMP
 OCP MAXIMUM.
  
 2} THERE IS NO SECONDARY OCP FOR "TLM" AS PANEL "LM" IS
 LISTED AS MAIN LUG ONLY. SEE 408.36 AND 450.3(B).
  
 3} THE LIGHTING CIRCUITS ARE NOT ON THE PANEL SCHEDULE
 AND DO NOT APPEAR TO BE CALCULATED AT 125% (CONTINUOUS
 LOAD) PER 215.2.
  
 4} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. THE DATE IS MISSING.
  
 5} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER PER
 61G15-23.002FLORIDA ADMINISTRATIVE CODE..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718