2008-03-05 17:41:37BUILDING PLAN REVIEW
 PERMIT: 08020593
 ADD: 580 VILLAGE BLVD. #304
 CONT: BIEBER CONST.
 TEL: (561)276-9966
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-5-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)F.S 481.221 ALL FINAL CONSTRUCTION DOCUMENTS AND
 INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS, PLANS,
 SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC RECORD
 SHALL BEAR THE SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE DOCUMENT AND THE
 DATE ON WHICH THEY WERE SEALED. THE SIGNATURE, DATE,
 AND SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT
 TO WHICH THEY ARE AFFIXED. THE DATE IS MISSING ON THE
 SEAL. THE CERTIFICATE OF AUTHORIZATION FOR THE
 DIFFERENT ENGINEERING AND ARCHITECTURAL FIRMS INDICATED
 ON THE PLANS IS REQUIRED TO BE SHOWN ON THE PLANS.
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)WHAT IS THE OCCUPANT LOAD OF THE SPACE? INDICATE
 THE SQUARE FOOTAGE OF THE NEW SPACE AND GIVE THE
 OCCUPANT LOAD USING TABLE 1004.1.2.
  
 5)FBC 11-7.2(2) (I) A PORTION OF THE RECEPTIONIST
 WINDOW SHALL BE A MINIMUM LENGTH OF 36 INCHES AND A
 MAXIMUM HEIGHT OF 36 INCHES. DETAILS #2 AND #4 ON SHEET
 A7.0 SHOW A HEIGHT OF 3'6" AT THE RECEPTIONIST WINDOW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676