| Plan Review Notes For Permit 08020581 |
| Permit Number |
08020581 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-27 15:07:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PROVIDE STRUCTURAL PLANS SHOWING GATE AND CATCH | | | POST CONSTRUCTION.NOT ENOUGH INFORMATION WAS | | | PROVIDED, FOR INSTANCE GAUGE, CONNECTIONS, PICKET | | | SPACING.IT IS NOT CLEAR TO WHAT EXTENT THE BOTTOM | | | SUPPORT WILL RESIST DEFLECTION, ESPECIALLY AS IT IS NOT | | | CLEAR WHAT THE "2X4" IS.ENGINEERING MAY BE | | | REQUIRED. | | | | | | 2.DECLARE WIND DESIGN CRITERIA FBC1603 AND GOVERNING | | | CODE. | | | | | | 3. INCLUDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN FBC*106.1.3. | | | | | | 4.PROVIDE A SURVEY SHOWING PROPOSED GATE LOCATION. | | | | | | 5.PROVIDE A REASONABLE VALUE FOR THIS PROJECT. | | | | | | |
|