Plan Review Notes
Plan Review Notes For Permit 08020549
Permit Number 08020549
Review Stop E
Sequence Number 2
Notes
Date Text
2008-04-22 14:23:30** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE EXACT NOTES FROM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW NOTES WITH RESPECT TO RE-SUB. SOME
 DOCUMENTS/INFORMATION WAS NOT SUBMITTED ON PREVIOUS
 REVIEW.
  
 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS REQUIRED
 UNDER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 IS NOT CODE
 COMPLIANT ON PLANS.
 THERE IS NOT ENOUGH INFORMATION FOR THE PROPOSED OVER
 RIDE MOTION SENSOR DEVICES.
 FOR EXAMPLE:
 PLEASE SEE LS 101 7.8.1.2.2 AND FBC 1016.1 AS THE
 DEVICE USED FOR NORMAL EGRESS LIGHTING SHALL BE FAIL
 SAFE ON AND MUST ALSO BE DUAL TECHNOLOGY. MAY NOT ONLY
 BE MOTION AS STATED ON PLANS. MUST ALSO STATE * FAIL
 SAFE ON*
 FOR EXAMPLE:
 PLEASE SEE THE PLANS INDICATE WHAT APPEAR TO BE
 STANDARD SWITCHES IN OTHER AREAS. THE SYMBOL LEGEND
 DOES NOT PROVIDE THE REQUIRED DEVICES.
  
 2) NOTE: PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON
 THE ENERGY CALCULATIONS NOW SUBMITTED AS METHOD *B*.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR.
 PLEASE SEE NOTES FROM PREVIOUS REVIEW AS IT STATES THE
 INFORMATION ON THE IDR MUST COMPLY WITH THE MINIMUM IN
 THE FBC AND ALL INFORMATION ON PLANS IS REQUIRED TO
 COORDINATE WITH THE ENERGY CALCULATIONS AND THE
 INFORMATION PLACED IN THE IDR. PLEASE SEE SOME ITEMS
 NOTED BELOW ARE EXAMPLES OF SPECIFIC ITEMS WHICH DO NOT
 CORRELATE. THIS IS IN NO WAY AN EXHAUSTED LIST OF ALL
 POSSIBLE ITEMS.
 FOR EXAMPLE:
 PLEASE SEE THE ELECTRICAL WATER HEATERS ON PLANS ARE
 NOT ON THE IDR. HOW IS IT POSSIBLE THAT THE IDR IS
 BLANK FOR WATER HEATERS?
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING ON THE WAREHOUSE PLANS STILL
 SHOWS THE FIXTURES AS *J*, AND THE IDR SHOWS FIXTURES
 AS ONE 514WATT FIXTURE. HOW IS THIS POSSIBLE? PLEASE
 SEE THE PRINT OUT FROM MANUFACTURE FOR THIS SAME
 FIXTURE AS LISTED ON THE FIXTURE LEGEND AS THIS FIXTURE
 BEING AN 8FT FIXTURE CONTAINS 4-32W BULBS. PLEASE SEE
 THE SPECS WHICH INDICATE 60W INPUT FOR EACH 4FT
 SECTION. BASED ON THE FIXTURES ON PLANS EVEN IF ALL
 FIXTURES IN WAREHOUSE WERE DONE AS ONE FIXTURE (WHICH
 IS NOT PERMITTED) THE TOTAL WATTAGE IS NOT ACCURATE
 WITH PLANS AND DOES NOT COORDINATE.
 FOR EXAMPLE:
 PLEASE SEE THE JURISDICTION IS LISTED AS PALM BEACH
 COUNTY WHEN THE SCOPE OF WORK IS LISTED IN CITY OF WEST
 PALM BEACH.
 FOR EXAMPLE:
 PLEASE SEE ITEMS FOR BUILDING WHICH WILL BE NOTED UNDER
 BUILDING REVIEW. DOORS SHOWN AS INSULATED ALUMINUM
 DOORS WHEN DOORS ARE GLASS. PLEASE SEE WALL SECTIONS OF
 THE IDR WHICH LISTS * METAL ROOF AND R-19 FOR A WALL.
 HOW IS THIS POSSIBLE?ITEMS LIKE THESE WILL BE PART OF
 MECH/ BLDG REVIEW AND ARE NOTED FOR INFORMATION.
  
 ** AS NOTED ABOVE THIS IS NOT AN EXHAUSTED LIST AND
 ITEMS ARE GIVEN AS A BENEFIT FOR INFORMATION TO GIVE
 EXAMPLES.
 13-415.2, 13-400.3.B, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING
 GIVEN AT THIS TIME. THIS IS ONLY A NOTICE.
 PLEASE KNOW SOME ELECTRICAL PLANS ALONG WITH ENERGY
 CALCULATIONS ARE BEING RETAINED BY THIS OFFICE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH WERE AT
 THE END OF THE REVIEW WHICH WERE LABELED AS
 *IMPORTANT*. THIS PREVIOUS NOTE REQUESTED THE
 OLD/VOIDED SHEETS TO BE RETURNED SEPARATE FOR
 REVIEW/COMPARISON OF CHANGES. THESE WERE NOT LOCATED IN
 SETS OF RESUBMITTED PLANS.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]