| 2008-04-22 14:23:30 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME OF THE EXACT NOTES FROM PREVIOUS |
| | REVIEW ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO SEE NEW NOTES WITH RESPECT TO RE-SUB. SOME |
| | DOCUMENTS/INFORMATION WAS NOT SUBMITTED ON PREVIOUS |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS REQUIRED |
| | UNDER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 IS NOT CODE |
| | COMPLIANT ON PLANS. |
| | THERE IS NOT ENOUGH INFORMATION FOR THE PROPOSED OVER |
| | RIDE MOTION SENSOR DEVICES. |
| | FOR EXAMPLE: |
| | PLEASE SEE LS 101 7.8.1.2.2 AND FBC 1016.1 AS THE |
| | DEVICE USED FOR NORMAL EGRESS LIGHTING SHALL BE FAIL |
| | SAFE ON AND MUST ALSO BE DUAL TECHNOLOGY. MAY NOT ONLY |
| | BE MOTION AS STATED ON PLANS. MUST ALSO STATE * FAIL |
| | SAFE ON* |
| | FOR EXAMPLE: |
| | PLEASE SEE THE PLANS INDICATE WHAT APPEAR TO BE |
| | STANDARD SWITCHES IN OTHER AREAS. THE SYMBOL LEGEND |
| | DOES NOT PROVIDE THE REQUIRED DEVICES. |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON |
| | THE ENERGY CALCULATIONS NOW SUBMITTED AS METHOD *B*. |
| | THE INPUT DATA REPORT WILL BE NOTED AS IDR. |
| | PLEASE SEE NOTES FROM PREVIOUS REVIEW AS IT STATES THE |
| | INFORMATION ON THE IDR MUST COMPLY WITH THE MINIMUM IN |
| | THE FBC AND ALL INFORMATION ON PLANS IS REQUIRED TO |
| | COORDINATE WITH THE ENERGY CALCULATIONS AND THE |
| | INFORMATION PLACED IN THE IDR. PLEASE SEE SOME ITEMS |
| | NOTED BELOW ARE EXAMPLES OF SPECIFIC ITEMS WHICH DO NOT |
| | CORRELATE. THIS IS IN NO WAY AN EXHAUSTED LIST OF ALL |
| | POSSIBLE ITEMS. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE ELECTRICAL WATER HEATERS ON PLANS ARE |
| | NOT ON THE IDR. HOW IS IT POSSIBLE THAT THE IDR IS |
| | BLANK FOR WATER HEATERS? |
| | FOR EXAMPLE: |
| | PLEASE SEE THE LIGHTING ON THE WAREHOUSE PLANS STILL |
| | SHOWS THE FIXTURES AS *J*, AND THE IDR SHOWS FIXTURES |
| | AS ONE 514WATT FIXTURE. HOW IS THIS POSSIBLE? PLEASE |
| | SEE THE PRINT OUT FROM MANUFACTURE FOR THIS SAME |
| | FIXTURE AS LISTED ON THE FIXTURE LEGEND AS THIS FIXTURE |
| | BEING AN 8FT FIXTURE CONTAINS 4-32W BULBS. PLEASE SEE |
| | THE SPECS WHICH INDICATE 60W INPUT FOR EACH 4FT |
| | SECTION. BASED ON THE FIXTURES ON PLANS EVEN IF ALL |
| | FIXTURES IN WAREHOUSE WERE DONE AS ONE FIXTURE (WHICH |
| | IS NOT PERMITTED) THE TOTAL WATTAGE IS NOT ACCURATE |
| | WITH PLANS AND DOES NOT COORDINATE. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE JURISDICTION IS LISTED AS PALM BEACH |
| | COUNTY WHEN THE SCOPE OF WORK IS LISTED IN CITY OF WEST |
| | PALM BEACH. |
| | FOR EXAMPLE: |
| | PLEASE SEE ITEMS FOR BUILDING WHICH WILL BE NOTED UNDER |
| | BUILDING REVIEW. DOORS SHOWN AS INSULATED ALUMINUM |
| | DOORS WHEN DOORS ARE GLASS. PLEASE SEE WALL SECTIONS OF |
| | THE IDR WHICH LISTS * METAL ROOF AND R-19 FOR A WALL. |
| | HOW IS THIS POSSIBLE?ITEMS LIKE THESE WILL BE PART OF |
| | MECH/ BLDG REVIEW AND ARE NOTED FOR INFORMATION. |
| | |
| | ** AS NOTED ABOVE THIS IS NOT AN EXHAUSTED LIST AND |
| | ITEMS ARE GIVEN AS A BENEFIT FOR INFORMATION TO GIVE |
| | EXAMPLES. |
| | 13-415.2, 13-400.3.B, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 3) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING |
| | GIVEN AT THIS TIME. THIS IS ONLY A NOTICE. |
| | PLEASE KNOW SOME ELECTRICAL PLANS ALONG WITH ENERGY |
| | CALCULATIONS ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH WERE AT |
| | THE END OF THE REVIEW WHICH WERE LABELED AS |
| | *IMPORTANT*. THIS PREVIOUS NOTE REQUESTED THE |
| | OLD/VOIDED SHEETS TO BE RETURNED SEPARATE FOR |
| | REVIEW/COMPARISON OF CHANGES. THESE WERE NOT LOCATED IN |
| | SETS OF RESUBMITTED PLANS. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |