| Plan Review Notes For Permit 08020549 |
| Permit Number |
08020549 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-23 12:11:24 | BUILDING PLAN REVIEW #2 | | | PERMIT: 08020549 | | | ADD: 5760 CORPORATE WAY #2-3-4 | | | CONT: O?CONNOR & TAYLOR INC. | | | TEL: (561)282-7492 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST 4-22-08 | | | ACTION: DENIED | | | | | | 1)OK | | | | | | 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) OK | | | 4)OK | | | | | | ** NEW** THE INPUT DATA REPORT FOR THE ENERGY | | | CALCULATIONS DO NOT MATCH THE PLANS. THE WALL SECTION | | | CONTAINS REFERENCES TO METAL ROOFING, THE DOORS WHICH | | | ARE SHOWN AS GLASS DOORS ON THE PLANS, ARE REFERENCE AS | | | INSULATED ALUMINIUM DOORS; THE INSULATION ON THE | | | DRAWINGS IS DIFFERENT TO WHAT IS STATED ON THE | | | CALCULATION SHEETS. THERE ARE OTHER ISSUES, SO PLEASE | | | MAKE THE CORRECTIONS ACCORDINGLY TO MATCH WHAT IS SHOWN | | | ON THE PLANS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX 561) 805-6726 | | | [email protected] |
|