2008-04-23 12:11:24BUILDING PLAN REVIEW #2
 PERMIT: 08020549
 ADD: 5760 CORPORATE WAY #2-3-4
 CONT: O?CONNOR & TAYLOR INC.
 TEL: (561)282-7492
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 4-22-08
 ACTION: DENIED
  
 1)OK
  
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
 4)OK
  
 ** NEW** THE INPUT DATA REPORT FOR THE ENERGY
 CALCULATIONS DO NOT MATCH THE PLANS. THE WALL SECTION
 CONTAINS REFERENCES TO METAL ROOFING, THE DOORS WHICH
 ARE SHOWN AS GLASS DOORS ON THE PLANS, ARE REFERENCE AS
 INSULATED ALUMINIUM DOORS; THE INSULATION ON THE
 DRAWINGS IS DIFFERENT TO WHAT IS STATED ON THE
 CALCULATION SHEETS. THERE ARE OTHER ISSUES, SO PLEASE
 MAKE THE CORRECTIONS ACCORDINGLY TO MATCH WHAT IS SHOWN
 ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX 561) 805-6726