| 2008-03-26 18:12:54 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT TI-1 BLDG DATA: BUILD-OUT SHALL BE DESIGNED TO |
| | FBC- 2004 W/2007 AMENDMENTS. PLEASE INDICATE ON PLANS. |
| | |
| | 2. SHT TI-1 INDICATES BOTH STORAGE OCCUPANCY, (13,392 |
| | SF), AND BUSINESS, (3,329 SF) TYPICAL SPACE. (SEE |
| | TYPICAL SPACE LIFE SAFETY TABULATIONS). PLEASE CLARIFY. |
| | IF THE SPACES ARE MIXED OCCUPANCY, INDICATE THE SQUARE |
| | FOOTAGE OF EACH OCCUPANCY IN EACH TYPICAL SPACE. |
| | |
| | 3. ALL MP & E SHEETS. THE ADDRESS IN THE TITLE BLOCK |
| | DOES NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA |
| | STATE DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCKS OR |
| | THE DBPR WEBSITE SO THE ADDRESS REFLECTS. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | |
| | 4. SHT MP--2 HOT WATER IS REQUIRE TO THE JANITOR SINKS |
| | PER SECTION 607.1. PLEASE SHOW COMPLIANCE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |