Plan Review Notes
Plan Review Notes For Permit 08020549
Permit Number 08020549
Review Stop P
Sequence Number 1
Notes
Date Text
2008-03-26 18:12:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT TI-1 BLDG DATA: BUILD-OUT SHALL BE DESIGNED TO
 FBC- 2004 W/2007 AMENDMENTS. PLEASE INDICATE ON PLANS.
  
 2. SHT TI-1 INDICATES BOTH STORAGE OCCUPANCY, (13,392
 SF), AND BUSINESS, (3,329 SF) TYPICAL SPACE. (SEE
 TYPICAL SPACE LIFE SAFETY TABULATIONS). PLEASE CLARIFY.
 IF THE SPACES ARE MIXED OCCUPANCY, INDICATE THE SQUARE
 FOOTAGE OF EACH OCCUPANCY IN EACH TYPICAL SPACE.
  
 3. ALL MP & E SHEETS. THE ADDRESS IN THE TITLE BLOCK
 DOES NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA
 STATE DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCKS OR
 THE DBPR WEBSITE SO THE ADDRESS REFLECTS. FAC
 61G15-23.002(2) & FS 471.025.
  
 4. SHT MP--2 HOT WATER IS REQUIRE TO THE JANITOR SINKS
 PER SECTION 607.1. PLEASE SHOW COMPLIANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  