Plan Review Notes
Plan Review Notes For Permit 08020549
Permit Number 08020549
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-31 16:01:41*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS,
 FIRE LANES)
  
 3.IN ADDITION TO THE ADDRESS NUMBERS ON THE EXTERIOR
 ELEVATION WHICH FRONTS CORPORATE WAY, THE TENANT SPACE
 NUMBERS SHALL BE SHOWN.AS PER WEST PALM BEACH CODE,
 THE UNIT NUMBERS (NOT TO BE INSTALLED ON THE FRONT
 DOORS) SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH. UNIT NUMBERS SHALL ALSO BE REQUIRED
 THE ON/AT THE REAR DOORS.FOR ADDRESSING MATTERS,
 CONTACT LILI URSU AT 561-822-1239
  
 4.CLASSIFY THE CONTENTS OF THE OCCUPANCY IN TERMS OF
 LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD DEPENDING
 ON THE CHARACTER OF MATERIALS STORED, THEIR PACKAGING,
 AND OTHER FACTORS.
  
 5.THE DOOR IN THE 1-HOUR RATED PARTITION BETWEEN THE
 BUSINESS AREA (OFFICE) AND THE STORAGE AREA (WAREHOUSE)
 SHALL BE A MINIMUM 20 MINUTE FIRE-RATING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722