Plan Review Notes
Plan Review Notes For Permit 08020549
Permit Number 08020549
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-10 08:03:22** DENIED REVIEW **
  
 PERMIT # 08020549
  
 1) NOTE: PLEASE SEE THE CODES LISTED ON COVER SHEET
 STATES 2001 FBC?
 PLEASE BE SURE THE ARCHITECTURAL SHEETS AND ELECTRICAL
 SHEETS.
 2004 FBC W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE SEE PLANS WHICH STATES * NEW BUILDING*
 YET BASED ON PLANS AND PERMIT APPLICATION THIS SEEMS TO
 BE FOR TENANT BLD OUTS.
 PLEASE KNOW ADDRESSING WILL BE NEEDED FOR SUITE/UNIT
 NUMBERS TO BE ASSIGNED. THIS WILL BE SENT TO ADDRESSING
 REVIEWER.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS
 IN NEED.
 A) PLEASE SEE13-400.3.A, HOW CAN METHOD *A* AS
 SUBMITTED BE USED WHEN THIS IS NOT FOR WHOLE BUILDING?
 PLEASE SEE 13-415.2.
 PLEASE SEE FIXTURE LEGEND ON PLANS IS NOT COMPLETE WITH
 THE NEW FIXTURES AND CAN NOT VERIFY ANY
 CALCULATIONS.(MISSING FIXTURE *J* ALL TOGETHER. PLEASE
 SEE THE NUMBER OF FIXTURES AND WATTAGES DO NOT
 CORRELATE.
 PLEASE SEE 13-415.2.ABC .1, .1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 AS
 NO LIGHTING CONTROL SYSTEMS WERE SUBMITTED.
 PLEASE SUBMIT COMPLETE DETAILS.
 PLEASE SEE SECTION ABOVE FOR SEPARATE SPACES AS PLANS
 SHOW NO DEVICES FOR COMPLIANCE.
 PLEASE SUBMIT MAXIMUM TIMES ON DEVICES.
 PLEASE SUBMIT TIME SCHEDULING ETC.
 THERE ARE MANY ITEMS MISSING AT THIS TIME WHICH CAN NOT
 BE REVIEWED.
  
 C) PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 FOR REQUIRED
 NOTES TO BE ON PLANS.
  
 4) NOTE: PLEASE SEE 600.5 AS THE MIN VA FOR SIGN
 CIRCUIT IS REQUIRED AT 1200VA.
  
 5) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW
 RECEPTACLE. PLEASE SEE 220.42 FOR LOADS.
  
 6) NOTE: PLEASE SEE MISSING CONTROLS AND CIRCUITING FOR
 EXTERIOR LIGHTS. ARE THESE ALL EXISTING AND FROM HOUSE
 PANEL? IF NOT PLEASE SEE 13-415.1.ABC.1.4 AS NOTED
 ABOVE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]