| 2008-03-10 08:03:22 | ** DENIED REVIEW ** |
| | |
| | PERMIT # 08020549 |
| | |
| | 1) NOTE: PLEASE SEE THE CODES LISTED ON COVER SHEET |
| | STATES 2001 FBC? |
| | PLEASE BE SURE THE ARCHITECTURAL SHEETS AND ELECTRICAL |
| | SHEETS. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | |
| | 2) NOTE: PLEASE SEE PLANS WHICH STATES * NEW BUILDING* |
| | YET BASED ON PLANS AND PERMIT APPLICATION THIS SEEMS TO |
| | BE FOR TENANT BLD OUTS. |
| | PLEASE KNOW ADDRESSING WILL BE NEEDED FOR SUITE/UNIT |
| | NUMBERS TO BE ASSIGNED. THIS WILL BE SENT TO ADDRESSING |
| | REVIEWER. |
| | |
| | 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS |
| | IN NEED. |
| | A) PLEASE SEE13-400.3.A, HOW CAN METHOD *A* AS |
| | SUBMITTED BE USED WHEN THIS IS NOT FOR WHOLE BUILDING? |
| | PLEASE SEE 13-415.2. |
| | PLEASE SEE FIXTURE LEGEND ON PLANS IS NOT COMPLETE WITH |
| | THE NEW FIXTURES AND CAN NOT VERIFY ANY |
| | CALCULATIONS.(MISSING FIXTURE *J* ALL TOGETHER. PLEASE |
| | SEE THE NUMBER OF FIXTURES AND WATTAGES DO NOT |
| | CORRELATE. |
| | PLEASE SEE 13-415.2.ABC .1, .1.1, .1.2 AND .1.3. |
| | |
| | B) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 AS |
| | NO LIGHTING CONTROL SYSTEMS WERE SUBMITTED. |
| | PLEASE SUBMIT COMPLETE DETAILS. |
| | PLEASE SEE SECTION ABOVE FOR SEPARATE SPACES AS PLANS |
| | SHOW NO DEVICES FOR COMPLIANCE. |
| | PLEASE SUBMIT MAXIMUM TIMES ON DEVICES. |
| | PLEASE SUBMIT TIME SCHEDULING ETC. |
| | THERE ARE MANY ITEMS MISSING AT THIS TIME WHICH CAN NOT |
| | BE REVIEWED. |
| | |
| | C) PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 FOR REQUIRED |
| | NOTES TO BE ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE 600.5 AS THE MIN VA FOR SIGN |
| | CIRCUIT IS REQUIRED AT 1200VA. |
| | |
| | 5) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW |
| | RECEPTACLE. PLEASE SEE 220.42 FOR LOADS. |
| | |
| | 6) NOTE: PLEASE SEE MISSING CONTROLS AND CIRCUITING FOR |
| | EXTERIOR LIGHTS. ARE THESE ALL EXISTING AND FROM HOUSE |
| | PANEL? IF NOT PLEASE SEE 13-415.1.ABC.1.4 AS NOTED |
| | ABOVE. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | |