| Plan Review Notes For Permit 08020546 |
| Permit Number |
08020546 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-24 13:35:47 | ****************PROVISO**************** | | | PER PHONE CONVERSATION WITH THE CBC, MR. PRATT THIS IS | | | AN EXACT FIXTURE CHANGE OUT OF PLUMBING FIXTURES (2 EA) | | | W/C, LAVS, AND SHOWER TRIM, WITH ONE NEW FIBERGLASS | | | SHOWER BASE WITH NO LAYOUT CHANGES. NOTE: THE | | | PREFABRICATED SHOWER SHALL CONFORM TO FBC PLUMBING | | | SECTION 417.1 APPROVAL: CONFORM TO ANSI Z124.2, ASME | | | A112.19.9M OR CSA B45.5 AND 417.4 SHOWER COMPARTMENTS: | | | MINIMUM 900 SQUARE INCHES REQUIRED (30" X 30") | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|