| Plan Review Notes For Permit 08020538 |
| Permit Number |
08020538 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-22 22:17:30 | *****DENIED***** | | | | | | 1.PLEASE INDICATE IF THE BUILDING HOUSES A SINGLE OR | | | MULTIPLE TENANTS. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 5.INDICATE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THIS | | | STRUCTURE. | | | | | | 6.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE | | | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE | | | HIGHWAY.AS PER WEST PALM BEACH CODE, NUMBERS SHALL BE | | | NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN | | | WIDTH. | | | | | | 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 8.SHOW THE LOCATION OF THE 2A:10 BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|