Plan Review Notes
Plan Review Notes For Permit 08020538
Permit Number 08020538
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-06 11:01:36** DENIEDREVIEW **
  
 1) NOTE: THE PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW ONCE SUBMITTING FOR PERMIT FOR CONSTRUCTION THIS
 MUST BE DONE BY A LICENSED CONTRACTOR. MAY NOT APPLY
 FOR PERMIT UNDER AN OWNER/BUILDER FOR PROPERTY AS
 LISTED.
 PLEASE SEE FS 489 PART 1.
 THE OWNER/BUILDER DISCLOSURE STATEMENT SUBMITTED HAS
 BEEN VOIDED
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON PLANS.
 FBC 2004 W/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE)
  
 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY NOTE THAT
 FBC CHAPTER 13 DOES NOT APPLY BECAUSE OF THE SIZE OF
 THE SPACE AND THE BUILDING.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE WHEN FBC CHAPTER 13
 DOES APPLY TO ANY SIZE BUILDING, LIGHTING CONTROLS IN
 BUILDINGS IS ONLY ONE PART TO FBC AND CHAPTER 13.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.1, .1.2, ETC (PLEASE BE SURE
 TO SEE MECHANICAL REVIEW COMMENTS)
 PLEASE SUBMIT AND SHOW LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 (BUILDING IS
 SHOWN OVER 5K SQ FT BASED ON AERIALS AND RECORDS.
  
 4) NOTE; PLEASE SEE PLANS CALL FOR EMERGENCY AND EXIT
 LIGHTS TO BE CIRCUITED TO LOCAL CIRCUITS HOWEVER BASED
 ON CIRCUITING AS SHOWN THIS IS NOT DONE.
 700.12F
 ** PANEL SCHEDULE EVEN INDICATES A DEDICATE CIRCUIT??
  
 5) NOTE: PLEASE CLARIFY RISER AS PANEL *A* IS SHOWN AS
 EXISTING YET RISER APPEARS TO BE SHOWN AS PROPOSED
 NEW?
 PLEASE SEE 230.2, 230.70, 230.71, 230.72 AS ONLY ONE
 SERVICE IS PERMITTED FOR THE BUILDING AND ALL MAINS ARE
 REQUIRED TO BE GROUPED.
 AS THE REMAINDER OF THE SERVICE FOR BUILDING ETC DOES
 NOT SHOW ANY OTHER ELECTRICAL THIS NEW SERVICE AS SHOWN
 IS NOT PERMITTED.
  
 6) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS.
 THIS WILL ALSO DEPEND ON SERVICE NOTE ABOVE.
 IN EITHER CASE LOAD CALCULATIONS AS STATED IN THE NEC
 220 NEEDS TO BE SHOWN.
 PLEASE SHOW TRACK LIGHTING LOADS AND HOW THEY WERE
 DETERMINED.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. RECEPTACLE
 LOADS, LIGHTING LOADS ETC.
 220.12, 220.14, 220.42, 220.44, 220.43, 215.3, 230.42
 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR MINIMUM AND ADDITIONAL
 INFORMATION.
  
 7) NOTE: PLEASE SEE 210.62 FOR ANY WINDOW AREAS WHICH
 WILL REQUIRE SHOW WINDOW RECEPTACLE(S). INCLUDE IN
 CALCULATIONS.
 *WINDOW ABOVE DOOR?*
  
 8) NOTE: PLEASE INCLUDE SUITE/UNIT # ON PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-05 21:03:482008-03-05 21:03:48
  
 IN ELEC FOR REVIEW. NOTES WILL FOLLOW ONCE REVIEW IS
 COMPLETED.