| Date |
Text |
| 2008-03-06 11:01:36 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: THE PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN |
| | REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE |
| | KNOW ONCE SUBMITTING FOR PERMIT FOR CONSTRUCTION THIS |
| | MUST BE DONE BY A LICENSED CONTRACTOR. MAY NOT APPLY |
| | FOR PERMIT UNDER AN OWNER/BUILDER FOR PROPERTY AS |
| | LISTED. |
| | PLEASE SEE FS 489 PART 1. |
| | THE OWNER/BUILDER DISCLOSURE STATEMENT SUBMITTED HAS |
| | BEEN VOIDED |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | ON PLANS. |
| | FBC 2004 W/2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (IF APPLICABLE) |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY NOTE THAT |
| | FBC CHAPTER 13 DOES NOT APPLY BECAUSE OF THE SIZE OF |
| | THE SPACE AND THE BUILDING. |
| | PLEASE EXPLAIN HOW THIS IS POSSIBLE WHEN FBC CHAPTER 13 |
| | DOES APPLY TO ANY SIZE BUILDING, LIGHTING CONTROLS IN |
| | BUILDINGS IS ONLY ONE PART TO FBC AND CHAPTER 13. |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2, ETC (PLEASE BE SURE |
| | TO SEE MECHANICAL REVIEW COMMENTS) |
| | PLEASE SUBMIT AND SHOW LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 (BUILDING IS |
| | SHOWN OVER 5K SQ FT BASED ON AERIALS AND RECORDS. |
| | |
| | 4) NOTE; PLEASE SEE PLANS CALL FOR EMERGENCY AND EXIT |
| | LIGHTS TO BE CIRCUITED TO LOCAL CIRCUITS HOWEVER BASED |
| | ON CIRCUITING AS SHOWN THIS IS NOT DONE. |
| | 700.12F |
| | ** PANEL SCHEDULE EVEN INDICATES A DEDICATE CIRCUIT?? |
| | |
| | 5) NOTE: PLEASE CLARIFY RISER AS PANEL *A* IS SHOWN AS |
| | EXISTING YET RISER APPEARS TO BE SHOWN AS PROPOSED |
| | NEW? |
| | PLEASE SEE 230.2, 230.70, 230.71, 230.72 AS ONLY ONE |
| | SERVICE IS PERMITTED FOR THE BUILDING AND ALL MAINS ARE |
| | REQUIRED TO BE GROUPED. |
| | AS THE REMAINDER OF THE SERVICE FOR BUILDING ETC DOES |
| | NOT SHOW ANY OTHER ELECTRICAL THIS NEW SERVICE AS SHOWN |
| | IS NOT PERMITTED. |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS. |
| | THIS WILL ALSO DEPEND ON SERVICE NOTE ABOVE. |
| | IN EITHER CASE LOAD CALCULATIONS AS STATED IN THE NEC |
| | 220 NEEDS TO BE SHOWN. |
| | PLEASE SHOW TRACK LIGHTING LOADS AND HOW THEY WERE |
| | DETERMINED. |
| | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. RECEPTACLE |
| | LOADS, LIGHTING LOADS ETC. |
| | 220.12, 220.14, 220.42, 220.44, 220.43, 215.3, 230.42 |
| | ETC |
| | FBC 106.3.5.1.2, 106.1.2 FOR MINIMUM AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 7) NOTE: PLEASE SEE 210.62 FOR ANY WINDOW AREAS WHICH |
| | WILL REQUIRE SHOW WINDOW RECEPTACLE(S). INCLUDE IN |
| | CALCULATIONS. |
| | *WINDOW ABOVE DOOR?* |
| | |
| | 8) NOTE: PLEASE INCLUDE SUITE/UNIT # ON PLANS. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE |
| | MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-03-05 21:03:48 | 2008-03-05 21:03:48 |
| | |
| | IN ELEC FOR REVIEW. NOTES WILL FOLLOW ONCE REVIEW IS |
| | COMPLETED. |