| 2008-03-18 09:37:58 | BUILDING PLAN REVIEW |
| | PERMIT: 08020538 |
| | ADD: 5301 S. DIXIE HWY |
| | CONT: PLAN REVIEW ONLY. |
| | TEL: (561)585-1701 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3-18-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| | BEACH ADMINISTRATIVE CODE. |
| | |
| | 3) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS |
| | & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 4) FL S S 713.13. NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 5) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 6)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS FOR THE |
| | EXTERIOR HOLLOW METAL DOOR AND THE STOREFRONT DOOR NEED |
| | SHALL BE APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | PLEASE HI-LIGHT OR CIRCLE THE DOOR WHICH WILL BE |
| | INSTALLED AT THE PROJECT FROM THE PRODUCT APPROVAL. |
| | |
| | 7) FBC 106.3.5 INDICATE ON THE DRAWINGS THE FOLLOWING |
| | INFORMATION. |
| | A)THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | B) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | C) THE OCCUPANT LOAD, SEE 1004. |
| | D) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED |
| | E) PROVIDE THE SCHEMATIC FOR THE FIRE SPRINKLER ON A |
| | CEILING PLAN IN RELATION WITH THE NEW WALLS. |
| | |
| | 8)ADDITIONAL INFORMATION IS REQUIRED FOR ALL NEW |
| | WALLS. ARE THE WALLS CONNECTED TO THE STRUCTURE ABOVE |
| | OF THE CEILING?SUBMIT A FRAMING DETAIL DRAWING FOR |
| | THE NEW EXTERIOR WALL SHOWING THE HEADER AND FLOOR |
| | ATTACHMENT WITH A UL# AND THE FIRE RATING OF THE WALL. |
| | |
| | 9)THERE IS NO BATHROOM OR DRINKING FOUNTAIN FACILITY |
| | SHOWN ON THE DRAWINGS, INDICATE THESE SYSTEMS ON THE |
| | DRAWINGS. THE DRINKING FOUNTAIN SHALL MEET THE |
| | REQUIREMENTS OF SECTION 11-4.15. FBC 11-4.17.2 WATER |
| | CLOSETS IN ACCESSIBLE STALLS SHALL COMPLY WITH SECTION |
| | 11-4.116. |
| | |
| | 10)TABLE 803.5 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR |
| | FINISH REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 11)SUBMIT A LIFE SAFETY PLAN SHOWING THE MEANS OF |
| | EGRESS, EXIT ACCESS, EXIT, TRAVEL DISTANCE ETC. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |