2008-07-23 16:20:26PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. WATER HEATER DETAILS; SHOW TYPE OF THERMAL
 EXPANSION TO BE USED PER SECTION 607.3. IF A HEATER PAN
 IS USED ON FIRST FLOOR A PAN DRAIN IS REQUIRED AND MUST
 GO OUTSIDE BUILDING SECTION 504.7.2.
  
 **RESPONSE NOTED AND COMMENT WAS PARTIALLY ADDRESSED,
 HOWEVER THE INSTALLATION OF A CHECK VALVE IS NOT
 PROTECTION AGAINST THERMAL EXPANSION.THE INSTALLATION
 OF AN EXPANSION TANK OR A CALIBRATED PRESSURE RELIEF
 VALVE ARE EXAMPLES OF A MEANS FOR THERMAL EXPANSION
 CONTROL. CLEARLY INDICATE THE LOCATION OF THE THERMAL
 EXPANSION CONTROL DEVICE USED ON RESUBMITTED P1 & P2
 SHEETS. PER FBC-PLUMBING SECTION 607.3.
  
 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3" TO
 SANITARY TEE SECTION 406.3.
  
 **RESPONSE NOTED, HOWEVER SHEET P1 FIRST FLOOR PLAN-
 PLUMBING IS STILL INDICATING THE WRONG BRANCH DRAIN
 PIPE SIZE OF 2" FOR THE WASHING MACHINE. PLEASE CORRECT
 AND CORRELATE WITH THE SANITARY RISER ON SHEET P2. PER
 FBC- PLUMBING SECTION 406.3.
  
 3. WATER RISER DIAGRAM; ONLY ON THE WATER HEATER
 SHOWN. T &P DISCHARGE PIPE TO BE 3/4" (ON WATER
 HEATER SHOWN) SHOCK ARRESTORS ARE NOT REQUIRED ON ALL
 FIXTURES, SEE SECTION 604.9.
  
 **RESPONSE NOTED AND COMMENT WAS PARTIALLY ADDRESSED,
 HOWEVER SHOCK ARRESTORS (WATER-HAMMER ARRESTORS) ARE
 REQUIRED TO BE INSTALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (EXAMPLES OF QUICK CLOSING VALVES ARE=
 WASHING MACHINES, DISHWASHERS, & ICE MAKERS). CLEARLY
 INDICATE THE REQUIRED WATER-HAMMER ARRESTORS ON BOTH
 THE HOT/COLD WATER SUPPLY TO THE WASHING MACHINE. THE
 RISER DIAGRAM INDICATES THE WATER-HAMMER ARRESTOR
 MISSING FROM THE HOT WATER SUPPLY TO THE WASHING
 MACHINE. WATER-HAMMER ARRESTOR IS ALSO REQUIRED ON THE
 HOT WATER SUPPLY TO THE DISHWASHER. PLEASE CORRECT THIS
 ON THE RESUBMITTAL. PER FBC- PLUMBING SECTION 604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730