| 2008-07-23 16:20:26 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. WATER HEATER DETAILS; SHOW TYPE OF THERMAL |
| | EXPANSION TO BE USED PER SECTION 607.3. IF A HEATER PAN |
| | IS USED ON FIRST FLOOR A PAN DRAIN IS REQUIRED AND MUST |
| | GO OUTSIDE BUILDING SECTION 504.7.2. |
| | |
| | **RESPONSE NOTED AND COMMENT WAS PARTIALLY ADDRESSED, |
| | HOWEVER THE INSTALLATION OF A CHECK VALVE IS NOT |
| | PROTECTION AGAINST THERMAL EXPANSION.THE INSTALLATION |
| | OF AN EXPANSION TANK OR A CALIBRATED PRESSURE RELIEF |
| | VALVE ARE EXAMPLES OF A MEANS FOR THERMAL EXPANSION |
| | CONTROL. CLEARLY INDICATE THE LOCATION OF THE THERMAL |
| | EXPANSION CONTROL DEVICE USED ON RESUBMITTED P1 & P2 |
| | SHEETS. PER FBC-PLUMBING SECTION 607.3. |
| | |
| | 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3" TO |
| | SANITARY TEE SECTION 406.3. |
| | |
| | **RESPONSE NOTED, HOWEVER SHEET P1 FIRST FLOOR PLAN- |
| | PLUMBING IS STILL INDICATING THE WRONG BRANCH DRAIN |
| | PIPE SIZE OF 2" FOR THE WASHING MACHINE. PLEASE CORRECT |
| | AND CORRELATE WITH THE SANITARY RISER ON SHEET P2. PER |
| | FBC- PLUMBING SECTION 406.3. |
| | |
| | 3. WATER RISER DIAGRAM; ONLY ON THE WATER HEATER |
| | SHOWN. T &P DISCHARGE PIPE TO BE 3/4" (ON WATER |
| | HEATER SHOWN) SHOCK ARRESTORS ARE NOT REQUIRED ON ALL |
| | FIXTURES, SEE SECTION 604.9. |
| | |
| | **RESPONSE NOTED AND COMMENT WAS PARTIALLY ADDRESSED, |
| | HOWEVER SHOCK ARRESTORS (WATER-HAMMER ARRESTORS) ARE |
| | REQUIRED TO BE INSTALLED WHERE QUICK CLOSING VALVES ARE |
| | UTILIZED. (EXAMPLES OF QUICK CLOSING VALVES ARE= |
| | WASHING MACHINES, DISHWASHERS, & ICE MAKERS). CLEARLY |
| | INDICATE THE REQUIRED WATER-HAMMER ARRESTORS ON BOTH |
| | THE HOT/COLD WATER SUPPLY TO THE WASHING MACHINE. THE |
| | RISER DIAGRAM INDICATES THE WATER-HAMMER ARRESTOR |
| | MISSING FROM THE HOT WATER SUPPLY TO THE WASHING |
| | MACHINE. WATER-HAMMER ARRESTOR IS ALSO REQUIRED ON THE |
| | HOT WATER SUPPLY TO THE DISHWASHER. PLEASE CORRECT THIS |
| | ON THE RESUBMITTAL. PER FBC- PLUMBING SECTION 604.9. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |