| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS |
| | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW: |
| | |
| | 3} 250.122(F)(1) BASED ON RATING OF OVERCURRENT |
| | PROTECTIVE DEVICE EACH PARALLEL EQUIPMENT GROUNDING |
| | CONDUCTOR SHALL BE SIZED ON THE BASIS OF THE AMPERE |
| | RATING OF THE OVERCURRENT DEVICE PROTECTING THE CIRCUIT |
| | CONDUCTORS IN THE RACEWAY OR CABLE IN ACCORDANCE WITH |
| | TABLE 250.122.SEE TABLE, THE #4 IN THE RISER DIAGRAM |
| | DOES NOT COMPLY.***SEE TABLE, A#3 IS REQUIRED FOR |
| | 400AMP OCP. |
| | |
| | 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 5} THE SERVICE GROUNDING ELECTRODE SYSTEM MUST BE RAN |
| | TO FOOTER STEEL TO COMPLY WITH 250.52(A)(3).INDICATE |
| | SAME ON RISER AND NOTES IN THE ELECTRICAL |
| | CALCULATION***THE RISER DIAGRAM INDICATES (2) 1/0 |
| | GROUND RODS, NOT CONDUCTOR SIZE. |
| | |
| | 12} THE LOCATION OF THE DISCONNECTS FOR THE AIR |
| | HANDLERS #1 & #2 DO NOT COMPLY WITH THE CLEARANCE |
| | REQUIREMENTS OF 110.26. |
| | |
| | FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE |
| | FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE LABEL THE |
| | ROOMS ON THE ELECTRICAL PLANS |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |