Plan Review Notes
Plan Review Notes For Permit 08020529
Permit Number 08020529
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-21 14:26:54 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW:
  
 3} 250.122(F)(1) BASED ON RATING OF OVERCURRENT
 PROTECTIVE DEVICE EACH PARALLEL EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE SIZED ON THE BASIS OF THE AMPERE
 RATING OF THE OVERCURRENT DEVICE PROTECTING THE CIRCUIT
 CONDUCTORS IN THE RACEWAY OR CABLE IN ACCORDANCE WITH
 TABLE 250.122.SEE TABLE, THE #4 IN THE RISER DIAGRAM
 DOES NOT COMPLY.***SEE TABLE, A#3 IS REQUIRED FOR
 400AMP OCP.
  
 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 5} THE SERVICE GROUNDING ELECTRODE SYSTEM MUST BE RAN
 TO FOOTER STEEL TO COMPLY WITH 250.52(A)(3).INDICATE
 SAME ON RISER AND NOTES IN THE ELECTRICAL
 CALCULATION***THE RISER DIAGRAM INDICATES (2) 1/0
 GROUND RODS, NOT CONDUCTOR SIZE.
  
 12} THE LOCATION OF THE DISCONNECTS FOR THE AIR
 HANDLERS #1 & #2 DO NOT COMPLY WITH THE CLEARANCE
 REQUIREMENTS OF 110.26.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE LABEL THE
 ROOMS ON THE ELECTRICAL PLANS
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  