| 2008-08-09 08:06:26 | |
| | |
| | DENIED |
| | |
| | 1)PROVIDE INSULATION VALUE FOR RAISED CONCRETE DECK |
| | ABOVE BREAKFAST AREA (BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACES). INCLUDE THIS AREA IN THE ENERGY |
| | CALCULATIONS. |
| | |
| | 2)SHOW METHOD OF OF WATERPROOFING OR MEMBRANE TO BE |
| | USED ON TERRACE DECK, IF A MEMBRANE SUCH AS MODIFIED |
| | BITUMEN ROOF PRODUCT IS USED SUBMIT PRODUCT APPROVAL |
| | WITH APPROPRIATE METHOD TO BE USED. |
| | |
| | 3)PRODUCT APPROVALS FOR THE PGT FIXED AND SINGLE HUNG |
| | WINDOWS ARE MISSING THE VALIDATION/INSTRUCTIONS THAT |
| | ARE PART OF THE STATE APPROVAL (IN THIS CASE MIAMI-DADE |
| | NOA), THEY ARE ALSO MISSING FOR THE PGT FRENCH DOORS |
| | AND THE GLASS BLOCK PRODUCTS. |
| | |
| | 4)PLEASE NOTE THAT THE ID MARK "A"USED FOR THE |
| | SECOND FLOOR TIE DOWN STRAP ON ENTRY ROOF IS A POURED |
| | IN TYPE STRAP AND THE WALLS ARE WOOD FRAME. |
| | |
| | 5)THE FLORIDA PRODUCT APPROVAL NUMBER FOR MGT GIRDER |
| | ANCHOR IS INCORRECT |
| | |
| | 6)INSERT THE STRAP/TIEDOWN INFORMATION SHEETS INTO |
| | THE PRODUCT APPROVAL SETS (SEE ATTACHED COPIES OF |
| | STRAPS BEING USED) |
| | |
| | 7)NO CONNECTOR WERE PROVIDED FOR EXTERIOR WOOD FRAME |
| | WALLS. |
| | |
| | 8)THE APPROVED ENGINEERED TRUSS DRAWINGS ARE DESIGNED |
| | FOR 140 MPH EXPOSURE B BUT THE BUILDING IS DESIGNED TO |
| | 140 MPH EXPOSURE C PLEASE CORRECT THE TRUSS DRAWINGS TO |
| | REFLECT DESIGNERS PARAMETERS. PLEASE NOTE THAT THE |
| | TRUSS DRAWINGS ARE NOT REQUIRE FOR PERMIT TO BE ISSUED |
| | BUT SIGNED AND SEALED APPROVED DRAWING ARE REQUIRED BY |
| | INSPECTOR BEFORE TRUSSES ARE SET. |
| | |
| | 9)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS |
| | WITH REVISIONS.PLEASE RE-SUBMIT ANY PAGES WITH THE |
| | IMPACT FEE STAMP ALONG WITH COPY OF COUNTY RECEIPT |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |