Plan Review Notes
Plan Review Notes For Permit 08020529
Permit Number 08020529
Review Stop B
Sequence Number 2
Notes
Date Text
2008-08-09 08:06:26 
  
 DENIED
  
 1)PROVIDE INSULATION VALUE FOR RAISED CONCRETE DECK
 ABOVE BREAKFAST AREA (BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES). INCLUDE THIS AREA IN THE ENERGY
 CALCULATIONS.
  
 2)SHOW METHOD OF OF WATERPROOFING OR MEMBRANE TO BE
 USED ON TERRACE DECK, IF A MEMBRANE SUCH AS MODIFIED
 BITUMEN ROOF PRODUCT IS USED SUBMIT PRODUCT APPROVAL
 WITH APPROPRIATE METHOD TO BE USED.
  
 3)PRODUCT APPROVALS FOR THE PGT FIXED AND SINGLE HUNG
 WINDOWS ARE MISSING THE VALIDATION/INSTRUCTIONS THAT
 ARE PART OF THE STATE APPROVAL (IN THIS CASE MIAMI-DADE
 NOA), THEY ARE ALSO MISSING FOR THE PGT FRENCH DOORS
 AND THE GLASS BLOCK PRODUCTS.
  
 4)PLEASE NOTE THAT THE ID MARK "A"USED FOR THE
 SECOND FLOOR TIE DOWN STRAP ON ENTRY ROOF IS A POURED
 IN TYPE STRAP AND THE WALLS ARE WOOD FRAME.
  
 5)THE FLORIDA PRODUCT APPROVAL NUMBER FOR MGT GIRDER
 ANCHOR IS INCORRECT
  
 6)INSERT THE STRAP/TIEDOWN INFORMATION SHEETS INTO
 THE PRODUCT APPROVAL SETS (SEE ATTACHED COPIES OF
 STRAPS BEING USED)
  
 7)NO CONNECTOR WERE PROVIDED FOR EXTERIOR WOOD FRAME
 WALLS.
  
 8)THE APPROVED ENGINEERED TRUSS DRAWINGS ARE DESIGNED
 FOR 140 MPH EXPOSURE B BUT THE BUILDING IS DESIGNED TO
 140 MPH EXPOSURE C PLEASE CORRECT THE TRUSS DRAWINGS TO
 REFLECT DESIGNERS PARAMETERS. PLEASE NOTE THAT THE
 TRUSS DRAWINGS ARE NOT REQUIRE FOR PERMIT TO BE ISSUED
 BUT SIGNED AND SEALED APPROVED DRAWING ARE REQUIRED BY
 INSPECTOR BEFORE TRUSSES ARE SET.
  
 9)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 WITH REVISIONS.PLEASE RE-SUBMIT ANY PAGES WITH THE
 IMPACT FEE STAMP ALONG WITH COPY OF COUNTY RECEIPT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  